Connecting a drain hose
1 . Connect the extended hose(drain hose) to connection part of the insulated drain hose by pushing it firmly .
2 . Seal the connection part between the extended drain hose and insulated drain hose with the insulator and then fix it .
Insulated drain hose
Insulator for extended drain hose
extended drain hose (not provided)
• As the indoor unit takes natural drainage, the drain hose should be installed in the downward direction .
• Make sure the drain hose is fixed with a cable tie . Otherwise, water leak may occur .
• Since foreign substances inside the drain board may block the drain pipe, all the foreign substances within the
drain board should be removed .
• When using the drain hose (extended hose), it should be integral type . Otherwise, water leak may occur
from the connection part of the extended hose . If it is necessary due to the short length of the hose, seal the
connection part with silicone sealant . (Do not use an insulating tape)
CAUTION
Leak test
1 . Pour water into the drain board or drain test hole of the indoor unit .
2 . Check that water is well drained at the end of the drain pipe .
3 . If water leaks, check that the indoor unit is installed on level ground and
connection of drain hose and drain pipe is correct . If not, proper action
should be taken .
Water bottle
• After connecting the drain pipe to the indoor unit, drainage test should be carried out . If the leak test is not
carried out correctly, water may enter the indoor area, which may cause property damage .
• When pouring water into the drain board or drain test hole, the water should not overflow .
• The leak test should be carried out at least for at least 24 hours .
CAUTION
ENGLISH-14
DVM PAC Mirage_IM_05674A-00_EN.indd 14