N
L
N
L
N
L
N
L
ELCB
MCCB+
ELB
V1
V2
Indoor Unit 1
Indoor Unit 2
Indoor Unit 3
Indoor Unit 4
Indoor Unit 5
Indoor Unit 6
Outdoor Unit
Wired Remote
Controller
EEV kit
K
Ceiling, wall-mounted indoor unit.
208-230V~
or
K
ELCB : Essential Installation
WARNING :
Power off before connecting any wires;
Indoor PBA will be damaged while V1,V2,F3,F4 short each
other.
19
ENGLISH
Wiring work
Power and communication cable connection
1. Before wiring work, you must turn off all power source.
2. Indoor unit power should be supplied through the breaker(MCCB, ELB) separated by the outdoor power.
3. The power cable should be used only copper wires.
4. Connect the power cable [1(L), 2(N)] among the units within maximum length and communication cable(F1, F2)
each.
5. Connect F3, F4(for communication) when installing the wired remote Control.