• When using A~J type of header joint, connect the header joint to the pipe with provided reducer.
• When using K~Z type of header joint, connect the header joint to the pipe by cutting the provided reducer
properly.
• Connect the header joint in order respecting the number of the indoor unit.
• Connect the indoor unit as the highest capacity comes first.
10~15mm
(0.39~0.59 inch)
or more
CAUTION
X
Install the header joint horizontally.
- Install the header joint horizontally so that it is not facing down.
Liquid side
±10°
or less
Should be
horizontal
Reducer
Header joint
Pipe
±15°
or less
Should be
horizontal
Should be
horizontal
Gas side
±15°
or less
Should be
horizontal
±10°
or less
Should be
horizontal