10
Installation location
Moving the Outdoor Unit
X
Select the moving route in advance.
X
Be sure that moving route is safe from the weight of the outdoor unit.
X
Do not slant the product more than 30˚ when carrying it. (Do not lay the product down sideways.)
X
The surface of the heat exchanger is sharp. Be careful not to get injured while moving and installing.
When moving with a crane or wire rope
X
When moving an outdoor unit to a higher place such as the rooftop.
- Fasten the wire rope as seen in the picture.
- Move the outdoor unit with the product packed to prevent possible product
damage during the transportation.
Wire rope/straps
Wood palette
When moving an outdoor unit with hands
X
Moving the outdoor unit by lifting up and carrying due to the short travel distance.
- Two people should carry the outdoor unit by holding transportation handle.
- Be careful not to damage the heat exchanger of the rear side of the outdoor unit during
transportation.
- Be careful not to get hurt by the sharp surface of the heat exchanger.
Installation and base ground work for an outdoor unit
X
Install the outdoor unit 150mm (6 inch) higher than the base ground and install the drain hole to connect the pipe to the
drainage.
X
When the front fan of an outdoor unit is installed in a place where the average snowfall is more than 150mm (6inch), the
discharge duct should be attached to the outdoor unit.
X
The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.
X
It is necessary to install wire mesh or steel bar when outdoor units are installed on a soft foundation.
X
When installing multiple outdoor units at the same place, install the
H beam on the base ground.
(When installing a number of outdoor units, you can install it on the
base ground.)
X
Install the H beam [150mm (6 inch) x 150mm (6 inch) x t10 : basic
specification] or vibration absorption frame to jut out from the base
ground.
X
After installing the H beam, apply corrosion protection.
X
Install a square pad [t=20mm (1 inch) or more] to prevent vibration
from the outdoor unit onto the base ground. Place the outdoor unit
on the H beam and fix it with the bolt, nut and washer. (Fix with M10
basic anchor bolt, nut and washer.)
Outdoor unit
Anchor bolt
Nut, Spring
washer
H beam
Square pad
A+10~20mm
(0.5~1 inch) or more
A
20mm
(1 inch)
75mm
(3 inch)
or more