23
English
Ins
tallation Pr
oc
edur
e
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Individual control of a
remote control
Heating setting compensation / Removing
condensated water in heating mode
EEV Step of stopped unit during oil
return/defrost mode
-
Indication
and Details
Indication
Details Indication
Details
Indication
Details
Indication
Details
Heating
Setting
Compensation
Removing
Condensated
Water in
Heating Mode
3
0 or 1
channel 1
0
Default (*5)
Disuse
0
Default value
2
channel 2
1
2 °C
Disuse
1
Oil return or Noise
decreasing in defrost mode
3
channel 3
2
5 °C
Disuse
4
channel 4
3
Default (*5) Use (*6)
4
2 °C
Use (*6)
5
5 °C
Use (*6)
(*)
Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1)
Minimizing fan operation when thermostat is off
– Fan operates for 20 seconds at an interval of 5 minutes in
Heat
mode.
(*2)
1: Fan is turned on continually when the hot water heater is turned on, 3: Fan is turned off when the hot water heater
is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the
Mode Select switch
(MCM-C200) on the outdoor unit and fix it as
Cool
mode.
(*3)
It is only for wall-mounted indoor unit with EEV Integrated. If any design condition meets either of the following
below, please set SEG11 to “7”.
a
The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than 20.
b
The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than “the
total of one(modular) system’s capacity(kW) / 2” (“the total of one(modular) system’s capacity(BTU/h) / 6800”).
ex) Outdoor capacity 28kW
→
28 /2 = 14. The total number of wall-mounted indoor units with EEV Integrated in
one (modular) system is more than 14.