※ When installing outdoor units in modul
e
, sele
c
t the po
w
er supply cable a
cc
ording to the sum of outdoor unit
capacity
.
(Refer to the table for each model)
※
P
o
w
er Supply
c
ords of parts of applian
c
es for outdoor use shall not be lig
h
ter than polychloroprene sheathed
fl
e
xible
c
or
d.
(
C
ode desig
n
ation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Ex
.
)
A
M500*
XVA
A
M120*
XVA
: 4 mm
2
A
M280*
XVA
: 16 mm
2
A
M500*
XVA
: 35 mm
2
①
②
③
A
M220*
XVA
A
M160*
XVA
A
M120*
XVA
②
③
①
EL
CB
MC
CB+ELB
or
• This device is intended for the connection to a power supply system with a maximum permissible system
impedance shown in the table (on the left page) at the interface point (power service box) of the user’s
supply .
• The user must ensure that this device is connected only to a power supply system which fulfills the
requirement above . If necessary, the user can ask the public power supply company for the system
impedance at the interface point .
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than
or equal to Ssc(*2) at the interface point between the user’s supply and the public system . It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a short-circuit power
Ssc greater than or equal to Ssc(*2) .
[Ssc (*2)]
Model
Ssc [MVA]
Model
Ssc [MVA]
AM080JXVHG
✴
3 .3
AM180JXVHG
✴
7 .6
AM100JXVHG
✴
4 .5
AM200JXVHG
✴
8 .1
AM120JXVHG
✴
5 .3
AM220JXVHG
✴
8 .6
AM140JXVHG
✴
5 .3
AM240HXVAG
✴
11 .7
AM160JXVHG
✴
6 .8
AM260HXVAG
✴
8 .6
Model
Ssc [MVA]
Model
Ssc [MVA]
AM080JXVAG
✴
3 .3
AM160JXVAG
✴
6 .8
AM100JXVAG
✴
4 .5
AM180JXVAG
✴
7 .6
AM120JXVAG
✴
5 .3
AM200JXVAG
✴
8 .1
AM140JXVAG
✴
5 .3
AM220JXVAG
✴
8 .6
NOTE
Caution for electrical work
• You must install ELCB or MCCB + ELB
- ELCB: Earth leakage breaker
- MCCB: Molded case circuit breaker
- ELB: Earth leakage breaker
• Do not operate the outdoor unit before completing the refrigerant pipe work .
• Do not disconnect or change the cable inside the product . It may cause damage to the product .
• Specification of the power cable is selected based on following installation condition; culvert installation/
ambient temperature 30 °C/ single multi conductor cables . If the condition is different from the ones
stated, please consult an electrical installation expert and re-select the power cable .
- If the length of power cable exceed 50m, re-select the power cable considering the voltage drop .
• Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer
cover) .
• Do not use the power cable with the core wire exposed due to insulator damage occurred during removal
of the sheath . When the core wire is exposed, it may cause fire .
Insulator (inner cover)
Exposed wire
core
<The example of exposed core wire>
Sheath (outer cover)
CAUTION
Installation
9
107
Содержание AM JXVHGH EU Series
Страница 52: ...Dimensional drawing Heat Pump High EER type AM080JXVHGH EU AM100JXVHGH EU AM120JXVHGH EU 4 52...
Страница 56: ...Dimensional drawing Heat Recovery High EER type AM080JXVHGR EU AM100JXVHGR EU AM120JXVHGR EU 4 56...
Страница 58: ...E Electrical wiring diagram Outdoor AM080a JXVAGH EU 5 5 58...
Страница 59: ...E Electrical wiring diagram Outdoor AM080 220JXVHGH EU AM240 260HXVAGH EU AM080 220JXVHGR EU 5 5 59...
Страница 97: ...Go Gw Go Gy PGl G G G G c G T eG c G G eG c G T eG MCU MCU MCU MCU MCU MCU Installation 9 97...
Страница 111: ...2016 11 Ver 1 7...