Outdoor unit capacity (kW)
*Maximum pipe length within 90m
(Main pipe diameter)
*Maximum pipe length over 90m
(Main pipe diameter)
Liquid pipe (mm)
gas pipe (mm)
Liquid pipe (mm)
gas pipe (mm)
22.4 kW
Ø 9.52
Ø 19.05
Ø 12.70
Ø 22.22
28.0 kW
Ø 22.22
Ø 25.40
note1)
33.6 kW
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
40.0 kW
45.0 kW
Ø 31.75
note2)
50.4 kW
Ø 15.88
Ø 19.05
56.0 kW
61.6 kW
67.2 kW
Ø 34.92
Ø 38.10
note3)
72.8 kW ~ 84.0 kW
Ø 19.05
Ø 22.22
89.6 kW ~ 95.2 kW
101.6 kW
Ø 41.28
Ø 41.28
106.6 kW ~ 135.2 kW
140.2 kW ~ 168.2 kW
Ø 53.98
173.6 kW ~ 224.8 kW
Ø 22.22
Ø 53.98
Ø 25.40
note1)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit
Indoor unit capacity (kW)
Branch pipe length within 45m
Branch pipe length between 45~90m
Liquid pipe (mm)
Gas pipe (mm)
Liquid pipe (mm)
Gas pipe (mm)
15.0 kW and below
Ø 9.52
Ø 15.88
Ø 12.70
Ø 19.05
Over 15.0 kW ~ 22.4 kW and below
Ø 19.05
Ø 22.22
Over 22.4 kW ~ 28.1 kW and below
Ø 22.22
Ø 25.40
note1)
Over 28.1 kW ~ 40.0 kW and below
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
Over 40.0 kW ~ 45.0 kW and below
Ø 31.75
note2)
Over 45.0 kW ~ 63.3 kW and below
Ø 15.88
Ø 19.05
Over 63.3 kW ~ 70.3 kW and below
Ø 34.92
Ø 38.10
note3)
Over 70.3 kW ~ 98.4 kW and below
Ø 19.05
Ø 22.22
Over 98.4 kW ~ 135.2 kW and below
Ø 41.28
Ø 41.28
Over 135.2 kW ~ 169.0 kW and below
Ø 53.98
Over 169.0 kW
Ø 22.22
Ø 53.98
Ø 25.40
note1)
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.
Installation
9
28 pipe.
89
Содержание AM JXVHGH EU Series
Страница 52: ...Dimensional drawing Heat Pump High EER type AM080JXVHGH EU AM100JXVHGH EU AM120JXVHGH EU 4 52...
Страница 56: ...Dimensional drawing Heat Recovery High EER type AM080JXVHGR EU AM100JXVHGR EU AM120JXVHGR EU 4 56...
Страница 58: ...E Electrical wiring diagram Outdoor AM080a JXVAGH EU 5 5 58...
Страница 59: ...E Electrical wiring diagram Outdoor AM080 220JXVHGH EU AM240 260HXVAGH EU AM080 220JXVHGR EU 5 5 59...
Страница 97: ...Go Gw Go Gy PGl G G G G c G T eG c G G eG c G T eG MCU MCU MCU MCU MCU MCU Installation 9 97...
Страница 111: ...2016 11 Ver 1 7...