9
ENGLISH
f
Module combination for AM192H
✴✴✴
J
✴
, AM216K
✴✴✴
J
✴
Model name for Combination
18 TON
34 TON
36 TON
AM216KXVGJ
✴
AM408KXVGJ
✴
AM432KXVGJ
✴
Number of individual outdoor units
1
2
2
Combined outdoor
unit
AM192H
✴✴✴
J
✴
(Large A type)
1
AM216K
✴✴✴
J
✴
(Large B type)
1
1
2
Nominal Capacity
Cooling(btu/h)
216000
408000
432000
Heating(btu/h)
243000
459000
486000
Rated Capacity
Cooling(btu/h)
206000
390000
415000
Heating(btu/h)
230000
435000
460000
Total capacity of
the connected
indoor
units(cooling)
Minimum(btu/h)
108000
204000
216000
Maximum(btu/h)
280800
530400
561600
Maximum number of connectable indoor units
37
64
64
f
Module combination for AM
✴✴✴
K
✴
Series
Model name for Combination
6 TON
8 TON
12 TON
14 TON
AM072KXVT
✴✴
AM096KXVT
✴✴
AM144KXVT
✴✴
AM168KXVT
✴✴
Number of individual outdoor units
1
1
2
2
Combined outdoor
unit
AM072
✴✴✴
1
2
1
AM096
✴✴✴
1
1
Nominal Capacity
Cooling(btu/h)
72000
96000
144000
168000
Heating(btu/h)
81000
108000
162000
189000
Rated Capacity
Cooling(btu/h)
69000
92000
138000
160000
Heating(btu/h)
77000
103000
154000
180000
Total capacity of the
connected indoor
units(cooling)
Minimum(btu/h)
36000
48000
72000
84000
Maximum(btu/h)
93600
124800
187200
218400
Maximum number of connectable indoor units
12
16
25
29
Model name for Combination
16 TON
18 TON
20 TON
22 TON
24 TON
AM192KXVT
✴✴
AM216KXVT
✴✴
AM240KXVT
✴✴
AM264KXVT
✴✴
AM288KXVT
✴✴
Number of individual outdoor units
2
3
3
3
3
Combined outdoor
unit
AM072
✴✴✴
3
2
1
AM096
✴✴✴
2
1
2
3
Nominal Capacity
Cooling(btu/h)
192000
216000
240000
264000
288000
Heating(btu/h)
216000
243000
270000
297000
324000
Rated Capacity
Cooling(btu/h)
184000
206000
228000
252000
276000
Heating(btu/h)
206000
230000
258000
282000
308000
Total capacity of the
connected indoor
units(cooling)
Minimum(btu/h)
96000
108000
120000
132000
144000
Maximum(btu/h)
249600
280800
312000
343200
374400
Maximum number of connectable indoor units
33
37
41
45
49
❋
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
❋
Minimum capacity of the indoor unit is 6.0 MBH.