47
ENGLISH
Classification
Example
Remarks
Maximum
allowable
length after
branch joint
First branch
joint ~ Farthest
Indoor unit
Pipe length
45m (148')
or less
Installing only with
Y-joint
b+c+d+e+f+g+p ≤ 45m (148')
-
Installing with Y-joint
and distribution header
i+k ≤ 45m (148')
Installing only with
distribution header
i ≤ 45m (148')
45m~90m
(148'~295')
Note 1)
Required conditions must be satisfied
-
EEV kit
Model name
Remarks
EEV Kit ~
Indoor unit
Actual pipe
length
2 m(6.6') or
less
MEV-E24SA
1 indoor
Apply to products without
EEV(Wall mounted & ceiling)
MEV-E32SA
20 m(66') or
less
MXD-E24K132A
2 indoor
MXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
❋
Please refer to the EEV Kit manual.
Note 1) Required condition
Classification
Condition
Example
First branch joint ~
Farthest Indoor unit
45 m (148') ≤ b+c+d+e+f+g+p ≤ 90 m (295'):
branch pipes (b, c, d, e, f, g) size must be increased
by 1 grade
Total length of
extended pipe
If the size of pipe (main pipe), between the first
branch joint and the outdoor unit, is not increased by
1 grade, a+(b+c+d+e+f+g)x2+h+i+j+k+l+m+n+p
≤ 1000 m (3281')
If the size of pipe (main pipe), between the first
branch joint and the outdoor unit, is increased by 1
grade, a+(b+c+d+e+f+g)x2+h+i+j+k+l+m+n+p ≤
1000 m (3281')
Each Y-joint ~ Each
indoor unit
h, i, j, … p ≤ 45 m (148')
Difference between the distance of the outdoor unit to the farthest indoor
unit and nearest indoor unit ≤ 45 m (148'), (a+b+c+d+e+f+g+p)-(a+h) ≤
45 m (148')
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110 m(361'), (If the
height difference is over 40 m(131'), contact your local dealer for more information.) but when the indoor unit is
located at lower level than outdoor unit, allowable height difference is 110 m (361') (If the height difference is over
50 m(164'), need to decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A