14
Space requirement for installation
Module installation
<Case 3>
O
ver 500
(20)
O
ver 500
(20)
O
ver 600
(24)
Over 100 (4) Over 100 (4)
Over 100 (4)
Over 100 (4)
Over 100 (4)
Over 100 (4) Over 100 (4)
Over 100 (4)
Front side
Front side
<Case 1>
<Case 2>
O
ver 200 (8)
O
ver 100 (4)
O
ver 300 (12)
[S2]
O
ver 500
(S1)
Over 100 (4)
Over 100 (4)
Over 100 (4)
Over 300 (12)
Over 400
(16)
Over 400
(16)
Height of
the wall is
unlimited
Front
side
Front side
❋
For <Case 1> or <Case 3>
• Height of the wall on the front side should not be higher than 1500mm (60 inch).
• Height of the wall on the air inlet side should not be higher than 500mm (20 inch).
• Height of the wall on the side is not limited.
• If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the exceeded
distance] should be added to the service space (S1, S2).
1500 (60)
h1
500 (20)
h2
Fr
ont side
Air inlet side
Unit: mm (inch)
S1+h1/2
S2+h2/2