30
Option SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Individual control of a
remote controller
Heating setting
compensation
EEV Step of stopped unit
during oil return/defrost
mode
Motion detect sensor
-
Remote
Controller
Display
Indication and
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
3
0 or 1
channel 1
0
Disuse
0
Default
value
0
Disuse
1
Turn out in 30min.
without motion
2
channel 2
1
2°C(35.6°F)
1
Oil return
or Noise
decreasing
in defrost
mode
2
Turn out in 60min.
without motion
3
channel 3
2
5°C(41°F)
3
Turn out in 120min.
without motion
4
channel 4
4
Turn out in 180min.
without motion
5
Turn out in 30min.
without motion or
*advanced function
6
Turn out in 60min.
without motion or
*advanced function
7
Turn out in 120min.
without motion or
*advanced function
8
Turn out in 180min.
without motion or
*advanced function
❋
Advanced function: Controlling cooling/heating current or power saving with motion detect.
■
05 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
5
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating
temp.
Offset
(When setting SEG3)
Standard cooling
temp.
Offset
(When setting SEG3)
Standard for mode
change Heating
→
Cooling
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
(When setting SEG3)
Standard for mode
change Cooling
→
Heating
(When setting SEG3)
Time required for
mode change
Compensation
option for Long pipe
or height difference
between indoor
units
-
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
-
-
-
-
-
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
-
-
-
-
-
Setting an indoor unit address and installation option
㨰䛙GiGkptluWZ_W^hOXPUGGGZW
YWXZTWZTW]GGG㝘㤸GXWaW\aYW