14
Performing leak test & insulation
Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU
f
You can contact the gas side and liquid side pipes but the pipes should not be
pressed.
f
When contacting the gas side and gas side pipe, use 1 grade thicker insulation.
Gas pipe
Liquid
pipe
Insulation
Insulation
Refrigerant pipe after EEV kit and MCU
f
Install the gas side and liquid side pipes, leave 10mm(0.39") of space.
f
When contacting the gas side and liquid side pipe, use 1 grade thicker
insulation.
Gas pipe
10mm(0.39")
Liquid pipe
10mm(0.39")
10mm(0.39")
• Install the insulation not to get wider and use the
adhesives on the connection part of it to prevent
moisture from entering.
• Wind the refrigerant pipe with insulation tape if it is
exposed to outside sunlight.
• Install the refrigerant pipe respecting that the insulation
does not get thinner on the bent part or hanger of pipe.
• Add the additional insulation if the insulation plate gets
thinner.
CAUTION
Additional
insulation
Hanger
Refrigerant pipe
insulation
a×3
a