24

 

Water leakage test

Pipe insulation

1.

Pour water to the hole for the drain test or drain pan of the 

indoor unit as shown in the figure.   (About 1ℓ)

2.

Make sure that draining is done properly by checking end 

of the drain pipe.

3.

If water leakage occurs, check the horizontality of the 

indoor unit, connection part of the drain hose/drain pipe 

and take measure to stop the leakage.

•   After connecting the drain pipe to the indoor unit,  

 

  you must perform leakage test.

 

  If the drain test has not done properly, water may get  

 

  into the indoor and cause property damage. 

•   Empty the condensation water in the drain pan 

 

  before any repair/maintenance service. 

•   You must insulate refrigerant pipes, branch joints, 

 

  distribution header and the pipe connection part.

•   Make sure to prevent any gap between the insulation 

 

  on the bent part of the pipes.

•   Make sure that insulation is overlapped when 

 

  fixing it.

 

 

 

Indoor unit

Fix securely without  

any gap.  

Power and communication cable connection

Wiring Work

1.

Before wiring work, you must turn off all power source.

2.

Indoor unit power should be supplied through the 

breaker ( ELCB or MCCB+ELB ) separated by the outdoor 

power.

ELCB: Earth Leakage Circuit Breaker

MCCB: Molded Case Circuit  Breaker

ELB: Earth Leakage Breaker

3.

The power cable should be used only copper wires.

4.

Connect the power cable{1(L), 2(N)} among the units within 

maximum length and communication cable(F1, F2) each.

5.

Connect F3, F4(for communication) when installing the 

wired remote control.

1.

Before wiring work, you must turn off all power source.

2.

Indoor unit power should be supplied through the 

breaker ( ELCB or MCCB+ELB ) separated by the outdoor 

power.

ELCB: Earth Leakage Circuit Breaker

MCCB: Molded Case Circuit  Breaker

ELB: Earth Leakage Breaker

3.

The power cable should be used only copper wires.

4.

Connect the power cable{1(L), 2(N)} among the units within 

maximum length and communication cable(F1, F2) each.

5.

Connect V1, V2 (for DC12V) and F3, F4(for communication) 

when installing the wired remote control.

ELCB 

MCCB+

ELB

Indoor Unit 1

Outdoor Unit

Indoor Unit 2

Indoor Unit 3

Wired Remote 

Control

220-240V~

or

ELCB 

MCCB+

ELB

Indoor Unit 1

Outdoor Unit

Indoor Unit 2

Indoor Unit 3

Wired Remote 

Control

220-240V~

or

  ELCB : Essential Installation

  WARNING :  Power off before connecting any wires;  

 Indoor PBA will be damaged while V1,V2,F3,F4 short  

 each other.

  ELCB : Essential Installation

  WARNING :  Power off before connecting any wires;  

 Indoor PBA will be damaged while V1,V2,F3,F4 short  

 each other.

 

AM



FNFDEH

 Series

 

AM



FBFDEH

 Series

NASA_Floor Stand_AM@@@FNFDEH@_IB,IM_EN_03677A-05.indd   24

2016-04-06   오후 2:25:15

Содержание AM***FNFDEH series

Страница 1: ...magine the possibilities Thank you for purchasing this Samsung product Floor Standing Unit AM FNFDEH AM FBFDEH IT FR ES EN PT NL EL DE HU PL DB68 03677A 06 NASA_Floor Stand_AM FNFDEH _IB IM_EN_03677A...

Страница 2: ...e summer but can also be an efficient heating method in the winter with the advanced Heat pump system This technology is up to 300 more efficient than electrical heating so you can further reduce its...

Страница 3: ...m Important safety symbols and precautions WARNING Hazards or unsafe practices that may result in severe personal injury or death CAUTION Hazards or unsafe practices that may result in minor personal...

Страница 4: ...cable Do not yank the power cable and touch the power plug with hands Potential risk of fire or electric shock Never use a damaged or dusted power plug power cable or loosened power receptacle Potent...

Страница 5: ...itioner Improper installation carries a risk of unit malfunction water leakage electric shock or fire If installing in specialty areas such as a factory complex or saline coastal area consult the plac...

Страница 6: ...ube When opening or closing the front panel use a stable stool and watch your steps carefully Disconnect the air conditioner from power supply before it is repaired or disassembled Clean the air condi...

Страница 7: ...r should not flow directly towards people pets and plants It is harmful to your health pets and plants Do not drink drain water coming out of the air conditioner Potential risk of health hazard Do not...

Страница 8: ...nditioner is working turn off the power source immediately Max current is measured according to IEC standard for safety and current is measured according to ISO standard for energy efficiency Check fo...

Страница 9: ...with the appliance For use in Europe This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowl...

Страница 10: ...lations in force with slings trucks scaffolding or any other means of elevation won t be considered in warranty and charged to end user Ensure the off on and protection switches are properly installed...

Страница 11: ...the product and its electronic accessories e g charger headset USB cable should not be disposed of with other household waste at the end of their working life To prevent possible harm to the environm...

Страница 12: ...l or warm with optimal efficiency Please read the user manual to get started and to make the best use of the air conditioner Floor Standing Unit Your air conditioner may look slightly different from t...

Страница 13: ...air conditioner will operate automatically in De ice mode for 10 minutes The steam produced on the outdoor unit in De ice mode is safe No intervention is required after about 10 minutes the air condi...

Страница 14: ...Washable air filter captures large particles from the air The filter is cleaned with a vacuum or by hand washing 1 Unscrew the screws 8 on the top of the indoor unit 2 Remove the front cabinet by unsc...

Страница 15: ...deformed when it is exposed to direct sunlight 6 Press the Filter Reset button on the remote controller Clean the Air filter every 2 weeks or when the filter indicator lights up on the remote control...

Страница 16: ...pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote control batteries 1 Outdoor unit Clean the heat exchanger on the outside of the unit 2 Clean the heat...

Страница 17: ...ttery The compressor will be off to protect internal battery when the air conditioner operates in Cool mode Protect compressor The air conditioner does not start operating immediately to protect the c...

Страница 18: ...change Check if you selected Auto or Dry mode The air conditioner automatically adjusts the fan speed to Auto in Auto Dry mode Timer function does not set Check if you press the Power button on the r...

Страница 19: ...he floor HEATING 27 C or less 20 C to 24 C Internal protection triggers and the air conditioner will stop DRYING 18 C to 32 C 5 C to 48 C Condensation may occur on the indoor unit with risk to have ei...

Страница 20: ...DEH EU 23 0 kg 945 220 600 mm AM056FBFDEH EU 28 5 kg 1225 220 600 mm AM071FBFDEH EU 28 5 kg 1225 220 600 mm Indoor unit NASA AM036FNFDEH EU 23 0 kg 945 220 600 mm AM056FNFDEH EU 28 5 kg 1225 220 600 m...

Страница 21: ...not fall or get shaken by vibration or any other external force 2 Drill a hole for the drain on the bottom or rear side of the indoor unit with a diameter between 60 65mm 3 Make sure that product is i...

Страница 22: ...installer to pressurize the whole system with nitrogen using a pressure regulator at a pressure above 4 1MPa gauge Leak test Performing LeakTest Insulation Discharge all the nitrogen to create a vacuu...

Страница 23: ...m entering Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hang...

Страница 24: ...se Circuit Breaker ELB Earth Leakage Breaker 3 The power cable should be used only copper wires 4 Connect the power cable 1 L 2 N among the units within maximum length and communication cable F1 F2 ea...

Страница 25: ...aximum length within 10 power drop among indoor units Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 coef 1 55 T Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running c...

Страница 26: ...etting status select the option as listed below Option setting is available from SEG1 to SEG 24 SEG1 SEG7 SEG13 SEG19 are not set as page option Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18...

Страница 27: ...6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each tim...

Страница 28: ...Fan button to enter SEG22 value Each time you press the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mo...

Страница 29: ...0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE SettingRMCaddress Groupchannel 16 Groupaddress Remote...

Страница 30: ...rs using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation Removing condensated water in heating mode EEVStepofstoppedunit duringoilre...

Страница 31: ...ps Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 Disuse 0 Disuse 0 Default value...

Страница 32: ...r SEG15 3 you need to use an external sensor or wired remote controller sensor to detect indoor temperature exactly 4 Default setting value 4Way Cassette Mini 4Way Cassette 5 C Other indoor units 2 C...

Страница 33: ...lectronicheaterintheflowchanneloftheindoorunitfan Air Flow Suction side Discharge side Electronic heater should not be installed Duct Indoor unit 05 series installation option SEG1 SEG2 SEG3 SEG4 SEG5...

Страница 34: ...C 1 0 5 C 1 1 5 C 2 1 C 2 1 C 2 2 C 3 1 5 C 3 1 5 C 3 2 5 C 4 2 C 4 2 C 4 3 C 5 2 5 C 5 2 5 C 5 3 5 C 6 3 C 6 3 C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE...

Страница 35: ...thermostat is on and turned off when the heating thermostat is off e g 2 Setting 02 series SEG15 2 Setting 05 series SEG18 A Room temp set temp f heating compensation temp External heater is turned on...

Страница 36: ...edvalue Indication 0 D 2 1 7 1 When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setti...

Страница 37: ...en using the centralized controller You don t have to set the SW03 and SW04 RMC switch when not using the centralized controller SW03 SW04 For Example When RMS address is set as 12 1 Before installing...

Страница 38: ...fy operatora www samsung com pl support IRAN 021 8255 www samsung com iran support HUNGARY 0680SAMSUNG 0680 726 786 0680PREMIUM 0680 773 648 www samsung com hu support SAUDI ARABIA 800 247 3457 800 24...

Отзывы: