32
Setting an indoor unit address and installation option(Continued)
* Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1)
Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
(*2)
1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fi x it as cool
mode.
(*3)
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will not be
output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fi x it as cool
mode.
❇
If Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wired
remote controller sensor to detect indoor temperature exactly.
(*4)
Default setting value
- 4Way Cassette, Mini 4Way Cassette: 5 °C
- Other indoor units: 2 °C
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Individual control of a
remote controller
Heating setting compensation / Removing
condensated water in heating mode
EEV Step of stopped
unit during oil return /
defrost mode
Motion detect sensor
-
Remote
Controller
Display
Indication and
Details
Indication
Details
Indication
Details
Indication
Details
Indication Details
Indication
Details
Heating Setting
Compensation
Removing
Condensated
Water in Heating
Mode
3
0 or 1
channel 1
0
Default
(*4)
Disuse
0
Default
value
0
Disuse
1
2 °C
Disuse
1
Turn out in 30min.
without motion
2
channel 2
2
5 °C
Disuse
1
Oil return
or Noise
decreasing
in defrost
mode
2
Turn out in 60min.
without motion
3
channel 3
3
Default
(*4)
Use
(*5)
3
Turn out in 120min.
without motion
4
channel 4
4
2 °C
Use
(*5)
4
Turn out in 180min.
without motion
5
5 °C
Use
(*5)
5
Turn out in 30min.
without motion or
*advanced function
6
Turn out in 60min.
without motion or
*advanced function
7
Turn out in 120min.
without motion or
*advanced function
8
Turn out in 180min.
without motion or
*advanced function
NASA_Floor Stand_AM@@@FNFDEH@_IB,IM_EN_03677A-05.indd 32