24
Wiring Work
Power and communication cable connection
1.
Before wiring work, you must turn off all power source.
2.
Indoor unit power should be supplied through the breaker(MCCB, ELB) separated by the outdoor power.
3.
The power cable should be used only copper wires.
4.
Connect the power cable{1(L), 2(N)} among the units within maximum length and communication cable(F1, F2)
each.
5.
Connect F3, F4(for communication) when installing the wired remote Control.
N
L
N
L
N
L
N
L
Indoor Unit 1
Outdoor Unit
Indoor Unit 2
Indoor Unit 3
Wired Remote
Control
220-240V~
❈
ELB : Essential Installation
EEV kit
Indoor Unit 4
Indoor Unit 5
Indoor Unit 6
❈
Ceiling, wall-mounted indoor unit.
Selecting compressed ring terminal
Silver solder
Norminal
dimensions for
cable (mm
2
)
Norminal
dimensions
for screw
(mm)
B
D
d1
E
F
L
d2
t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
Min.
Max.
Standard
dimension
(mm)
Allowance
(mm)
Min.
1.5
4
6.6
±0.2
3.4
+0.3
-0.2
1.7
±0.2
4.1
6
16
4.3
+0.2
0
0.7
4
8
2.5
4
6.6
±0.2
4.2
+0.3
-0.2
2.3
±0.2
6
6
17.5
4.3
+0.2
0
0.8
4
8.5
4
4
9.5
±0.2
5.6
+0.3
-0.2
3.4
±0.2
6
5
20
4.3
+0.2
0
0.9