Samsung AM***FN*D series Скачать руководство пользователя страница 28

27

A

ENGLISH

Drain pipe and drain hose installation

1

The drain pipe should be installed within 11.81inch(300mm) to 21.65inch(550mm) from the flexible hose 
and then lift down 0.79inch(20mm) or more.

2

Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 
3.28~4.92ft(1.0~1.5m).

3

Install the air vent in the horizontal drainpipe to prevent water flow back to the indoor unit.

You may not need to install it if there were proper slope in the horizontal drainpipe.

Note

4

The flexible hose should not be installed upward position, it may cause water flow back to the 

indoor unit.

With the drain pump

1

Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 
3.28~4.92ft(1~1.5m).

2

Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.

3

Do not install the drainpipe to upward position. It may cause water flow back to the unit.

Without the drain pump

3.28~4.92ft

(1~1.5m)

Horizontal drainpipe
more than 1/100 slope

Ceiling

Hanger

Flexible hose

Flexible hose

Air vent

11.8inch(300mm) or less

Horizontal drainpipe
more than 1/100 slope

Within

11.81~21.65inch 

(300~550mm)

3.28~4.92ft

(1~1.5m )

7.87inch

(200mm) 

or more

Ceiling

Hanger

0.79inch

(20mm)or more

Drainpipe Connection

Содержание AM***FN*D series

Страница 1: ...ioner User manual AM777FN7D77 AM777JNM77 AM777MN7D77 ŷ Thank you for purchasing this Samsung air conditioner ŷ Before operating this unit please read this user manual carefully and retain it for future reference ...

Страница 2: ......

Страница 3: ...21 Cutting flaring the pipes 23 Performing leak test insulation 24 Drain pipe and drain hose installation 26 Wiring work 30 Setting an indoor unit address and installation option 33 Setting temperature control of discharge air 44 Final check and trial operation 44 Providing information for user 45 Troubleshooting 45 Adjusting air flow 47 Extending the power cable 53 ...

Страница 4: ...ontact SAMSUNG s technical support if the unit produces smoke if the power cable is hot or damaged or if the unit is very noisy X Always remember to inspect the unit electric connections refrigerant tubes and protections regularly These operations should be performed by qualified personnel only XThe unit contains moving parts which should always be kept out of the reach of children X Do not attemp...

Страница 5: ...ant with the electric specifications and with the instructions provided in the wiring scheme Always verify that all connections comply with the standards applicable to the installation of air conditioners X Make sure that you earth the cables Do not connect the earth wire to the gas pipe water pipe lighting rod or telephone wire If earthing is not complete electric shock or fire may occur X Instal...

Страница 6: ...nclude the last four accessories Insulation cover Thermal insulation A use for refrigerant pipe Thermal insulation B use for refrigerant pipe Thermal insulation use for drain hose User s manual Installation manual Flexible hose clamp Grommet Cable tie Flexible hose Reducer NIPPLE CONNECTOR 3 8 ĺ1 4 NIPPLE CONNECTOR 5 8 ĺ1 2 FASTENER NUT FLARE 1 4 FASTENER NUT FLARE 1 2 ...

Страница 7: ...eck up must be made to take service clean and repair the unit z It is possible to install the unit at an height of between 7 3 8 3ft 2 2 2 5m from the ground if the unit has a duct with a well defined lenght 11 81inch 300mm or more to avoid fan motor blower contact X Construction Standard for Inspection Hole 1 In case the ceiling is textile Inspection hole dose not need 2 In case the ceiling is pl...

Страница 8: ...25 59 14 17 650x360 HSP Duct AM7FNHD7 70367 70487 47 24 x25 59 14 17 1200x650x360 47 24 25 59 1200x650 47 24 25 59 1200x650 25 59 14 17 650x360 25 59 14 17 650x360 MSP Duct AM7JNMD7 AM7JNMP7 Drain pump built in 7D7 70077 70097 70127 70157 70187 7P7 70067 45 28 18 90 x12 60 1150x480x320 45 28 18 90 1150x480 45 28 18 90 1150x480 18 90 12 60 480x320 18 90 12 60 480x320 7P7 70187 70287 70427 47 24 x25...

Страница 9: ...wer supply connection 7 Air discharge grille flange 8 Hook ø9 52 3 8 or M10 11 9 0 47 3 256 768 30 14 2 80 71 3 94 100 0 39 10 938 4 36 94 Suspension position 600 23 62 477 18 78 Suspension position 8 100 800 31 50 860 33 86 Air outlet duct flange 900 35 43 22 0 87 ø3 2 0 13 Hole 28 1 1 All around Discharge side Suction side 199 7 83 151 6 5 97 100 3 94 182 7 17 246 9 69 18 0 71 OD32 1 26 30 5 1 2...

Страница 10: ...connection 7 Air discharge grille flange 8 Hook ø9 52 3 8 or M10 AM018 024FNLD777 12 9 0 51 3 322 966 38 03 1138 44 80 Suspension position 477 18 78 Suspension position 10 100 1000 39 37 1060 41 73 Air outlet duct flange 1100 43 31 26 1 02 ø3 2 0 13 Hole All around Discharge side Suction side 2 80 71 3 94 100 0 39 10 600 23 62 28 1 1 28 1 1 199 7 83 151 6 5 97 100 3 94 182 7 17 246 9 69 18 0 71 OD...

Страница 11: ... discharge grille flange 8 Hook ø9 52 3 8 or M10 AM030 036 048FNLD777 15 9 0 63 4 290 1160 45 67 3 27 83 2 88 176 6 93 0 39 10 1338 52 68 Suspension position 690 27 17 477 18 78 Suspension position 12 100 1200 47 24 1260 49 61 Air outlet duct flange 1300 51 18 32 1 26 ø3 2 0 13 Hole All around Discharge side Suction side 295 11 61 247 6 9 75 2 100 200 7 87 186 7 32 250 9 84 337 13 27 18 0 71 29 1 ...

Страница 12: ...ODØ1 05 26 67 5 Power supply Communication connection 6 Air discharge grille flange 7 Suction flange 8 Hook ø9 52 3 8 or M10 76 2 99 132 5 19 139 5 47 480 18 90 397 15 63 Suspension position 260 10 23 185 7 28 90 3 54 936 36 85 Suspension position 900 35 43 844 33 23 Air outlet duct flange 135x5 675 26 57 12 0 47 77 3 00 117 4 61 6 8 7 5 4 3 2 1 530 20 87 900 35 43 1000 39 37 500 19 68 97 3 82 87 3...

Страница 13: ...26 67 5 Power supply Communication connection 6 Air discharge grille flange 7 Suction flange 8 Hook ø9 52 3 8 or M10 2 1 3 4 5 6 7 8 397 15 63 Suspension position Suction side Discharge side 1186 46 69 Suspension position 1150 45 28 902 35 51 Air outlet duct flange 135 6 810 31 89 222 8 74 82 3 23 137 5 39 149 5 87 480 18 90 27 1 06 107 4 21 157 6 18 320 12 60 229 9 02 125 4 92 87 3 43 1250 49 21 ...

Страница 14: ...on With drain pump 3 4 ODØ1 05 26 67 5 Power supply Communication connection 6 Air discharge grille flange 7 Suction flange 8 Hook ø9 52 3 8 or M10 Suction side Discharge side 1186 46 69 Suspension position 1150 45 28 1000 39 37 Air outlet duct flange 6 150 900 35 43 Unit mm inch 397 15 63 Suspension position 480 18 90 530 20 87 1250 49 21 1150 45 28 222 8 74 87 3 43 500 19 69 27 1 06 107 4 21 157...

Страница 15: ... 52 3 8 or M10 AM048FNMD 777 AM036 048FNHD 777 Unit mm inch 7 8 6 4 3 2 1 5 534 21 02 Suspension position Suction side Discharge side 360 14 17 253 9 96 Air outlet duct flange 2 100 200 7 87 80 3 15 170 6 69 244 9 61 299 11 77 OD32 1 26 28 1 10 121 4 76 137 5 39 20 0 79 ø3 2 0 13 hole All around 1236 48 66 Suspension position 1200 47 24 1000 39 37 Air outlet duct flange 6 150 900 35 43 222 8 74 86...

Страница 16: ... 7 Suction flange 8 Hook ø9 52 3 8 or M10 AM024 027 030 036 048 054JNHD 777 AM018 028 042JNMP 777 Drain pump built in Unit mm inch 7 6 8 5 4 1 2 3 534 21 02 Suspension position Suction side 1236 48 66 Suspension position 1200 47 24 1162 45 75 Air outlet duct flange 4 200 800 31 50 650 25 59 700 27 56 1300 51 18 1200 47 24 500 19 69 Discharge side 222 8 74 86 3 39 80 3 15 170 6 69 244 9 61 299 11 7...

Страница 17: ...filter 7 Hook M8 M10 Unit inch mm 7 28 185 6 22 158 5 75 146 27 56 700 7x3 937 27 56 7x100 700 32 17 817 33 46 850 22 ø0 13 3 2 35 43 900 23 78 604 27 56 700 19 69 500 33 46 850 37 40 950 8 66 220 2x3 543 7 09 2x90 180 9 84 250 8 39 213 4 92 125 13 39 340 Inspection hole Air outlet duct flange Suspension position Discharge side Suction side hole Air around Suspension position AM007 009 012 015 018...

Страница 18: ...lter 7 Hook M8 M10 7 28 185 6 22 158 5 83 148 27 56 700 23 78 604 11x3 937 43 31 11x100 1100 45 94 1167 47 24 1200 30 ø0 13 3 2 49 21 1250 27 56 700 19 69 500 47 24 1200 51 18 1300 8 66 220 2x3 543 7 09 2x90 180 9 84 250 8 39 213 4 92 125 13 39 340 Inspection hole Air outlet duct flange Suspension position Discharge side Suction side hole Air around Suspension position AM024 027 030MNHD 777 Drain ...

Страница 19: ... 53 7 06 2x115 230 Inspection hole Air outlet duct flange Suspension position Discharge side Suction side hole Air around Suspension position Unit inch mm No Name Description 1 Liquid pipe connection ø3 8 9 52 2 Gas pipe connection ø5 8 15 88 3 Drain pipe connection 3 4 ODØ1 05 26 67 4 Power supply connection 5 Air discharge flange 6 Air filter 7 Hook M8 M10 Selecting the installation location AM0...

Страница 20: ...on bolt X If the length of suspension bolt is more than 4 92ft 1 5m it is required to prevent vibra tion X If this is not possible create an opening on the false ceiling in order to be able to use it to perform the required operations on the indoor unit 4 Screw eight nuts to the suspension bolts making space for hanging the indoor unit X You must install the suspension bolts more than four when in...

Страница 21: ...36 048JNHDCH 2 Pad Cushion should be removed before installing air conditioner Caution Noise will increase 3 6 dB A when the air flow enters from the bottom side Only for Slim Duct Type product Caution Air Flow Indoor unit installation ...

Страница 22: ...and shape are subject to change according to the model AM77FNLD777 AM77FNMD777 AM77FNHD777 AM77JNMD777 AM77JNHD777 AM77JNMP777 Purging the unit AM77MNMD777 AM77MNHD777 There are two refrigerant pipes of differing diameters X A smaller one for the liquid refrigerant X A larger one for the gas refrigerant X The inside of copper pipe must be clean has no dust The connection procedure for the refriger...

Страница 23: ...n the flaring area to prevent a leak 2 Be sure that there must be no crack or kink on the bended area K The designs and shape are subject to change according to the model A Liquid refrigerant port Gas refrigerant port Drain hose connection port A Gas refrigerant port Liquid refrigerant port Drain hose connection port AM77FNLD777 AM77FNMD777 AM77FNHD777 AM77JNMD777 AM77JNHD777 AM77JNMP777 Drain pum...

Страница 24: ... the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque Outer diameter D Depth of flaring part A Using flaring tool for R 410A Using conventional flaring tool Clutch type Wing nut type mm inch mm inch mm inch mm inch 6 35 1 4 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 9 52 3 8 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 12 70 1 2 ...

Страница 25: ...ain pump built in No gap NBR T13 0 0 51 or thicker Insulation cover pipe Indoor unit Be sure to overlap the insulation Insulation pipe Mustfittightlyagainstbody withoutanygap Caution Discharge all the nitrogen to create a vacuum and charge the system Caution Once you have checked that there are no leaks in the system you can insulate the piping and hose 1 To avoid condensation problems place T13 0...

Страница 26: ...a dormitory and studio or near an exit that opens and closes frequently The place where the pipe is installed is highly humid due to the lack of ventilation system RefrigerantpipebeforeEEVkitandMCUorwithoutEEVkitandMCU X You can contact the gas side and liquid side pipes but the pipes should not be pressed X When contacting the gas side and gas side pipe use 1 grade thicker insulator Refrigerant p...

Страница 27: ...lled drain hose must be insulated fully by heat insulating material To be provided at site 3 While using draining pump insulate the drain hose with heat insulating material according to the figure note X Check if the rubber ring is installed properly on the draining pump X Check if the drain cap blocks the outfall of drain pan properly Caremustbetakenwheninstallingthedrainhosefortheindoorunittoens...

Страница 28: ... be installed upward position it may cause water flow back to the indoor unit With the drain pump 1 Install horizontal drainpipe with a slope of 1 100 or more and fix it by hanger space of 3 28 4 92ft 1 1 5m 2 Install U trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit 3 Do not install the drainpipe to upward position It may cause water flow back to the unit Withou...

Страница 29: ...or unit from the main drain when installed indoor units are more than 3 2 You may need to install individual air vent to prevent water flow back at the top of each indoor unit drainpipe With the drain pump Drain pipe and drain hose installation 3 94inch 100mm or more Ceiling Horizontal drainpipe more than 1 100 slope Main drainpipe Hanger Main air vent Centralized horizontal drainpipe more than 1 ...

Страница 30: ...nage test should be done after installation has been finished To avoid water overflow from the indoor unit because the drain tube is blocked Note Reinstall the side cover plate 7 Check drain water drops at the end of the drain pipe 5 Make sure there is no water leak at the drainage 6 Drainpipe Drain water drops AM77FNLD777 AM77FNMD777 AM77FNHD777 K The designs and shape are subject to change accor...

Страница 31: ...nch Standard dimension inch Allowance inch Standard dimension inch Allowance inch Min Min Max Standard dimension inch Allowance inch Min 0 0023 0 16 0 26 0 0079 0 13 0 012 0 0079 0 067 0 0079 0 16 0 24 0 63 0 17 0 0079 0 0 028 0 16 0 31 0 0039 0 16 0 26 0 0079 0 17 0 012 0 0079 0 091 0 0079 0 24 0 24 0 69 0 17 0 0079 0 0 031 0 16 0 33 0 0062 0 16 0 37 0 0079 0 22 0 012 0 0079 0 134 0 0079 0 24 0 2...

Страница 32: ...mm2 inch2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Example of Installation Total power cable length L 328ft 100m Running current of each units 1 A Total 10 indoor units were installed X Apply following equation Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 K Calculation O Installing with 1 sort wire O Installing with 2 different sort wire 10 A Ind...

Страница 33: ...over 10 of supply rating the indoor unit is protected stopped and the error mode indicates X To protect the product from water and possible shock you should keep the power cable and the connection cord of the indoor and outdoor units in the iron pipe X Connect the power cable to the auxiliary circuit breaker An all pole disconnection from the power supply must be incorporated in the fixed wiring 1...

Страница 34: ...tion setting is available from SEG1 to SEG 24 X SEG1 SEG7 SEG13 SEG19 are not set as page option X Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18 SEG20 24 as OFF status SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 0 X X X X X 1 X X X X X SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X On SEG1 12 Off SEG13 24 Mode Selects ope...

Страница 35: ...tion 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG11 SEG12 option Press Low Fan button to enter SE...

Страница 36: ...ion 14 Setting Dry mode Press Mode button to be change to Dry mode in the OFF status 15 Setting SEG18 SEG20 option Press Low Fan button to enter SEG18 value Press High Fan button to enter SEG20 value Each time you press the button will be selected in rotation 16 Setting Fan mode Press Mode button to be change to Fan mode in the OFF status 17 Setting SEG21 SEG22 option Press Low Fan button to enter...

Страница 37: ...indoor unit Theunitdigitof anindoorunit Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE __ SettingRMCaddress __ Groupchannel 16 Groupaddress Indication andDetails...

Страница 38: ...when heating stops SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output External heater On or Off signal Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation Removing condensated water in heating mode EEV Step of stopped unit during oil return defrost mode X 1 WAY 2WAY 4WAY DUCT MO...

Страница 39: ...compensation Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Useof External room temperature sensor Minimizing fanoperation when thermostat isoff 0 2 0 Disuse Disuse 0 Disuse 0 Disuse 1 Use Disuse 1 RPM compensation 2 Disuse Use 1 1 Use 2 Highceiling KIT 3 Use Use 1 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Useofdr...

Страница 40: ... 0 Disuse 0 Thermoon 0 Usebuzzer 2 1000Hour 1 ON OFF control 1 Operation on 1 Disusebuzzer 6 2000Hour 2 OFF control 2 Use 3 3 Window ON OFF control 3 Use 3 Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Explanation PAGE Individualcontrolof aremotecontroller Heatingsettingcompensation EEVStepofstopped unitduringoilreturn defrostmode Indication andDetails Indication Details Indication Details Indication...

Страница 41: ...nisturnedoncontinuallywhenthehotwaterheateristurnedon 3 Fanisturnedoffwhenthehotwaterheateristurnedonwithcoolingonlyindoorunit Coolingonlyindoorunit Tousethisoption installtheModeSelectswitch MCM C200 ontheoutdoorunitandfixitascoolmode 3 Whenthefollowing2or3isusedasexternalheaterOn Offsignal thesignalformonitoringexternalcontactcontrolwillnotbeoutput 2 Fanisturnedoncontinuallywhentheexternalheater...

Страница 42: ... 4 5 4 F 3 C 5 4 5 F 2 5 C 5 4 5 F 2 5 C 5 6 3 F 3 5 C 6 5 4 F 3 C 6 5 4 F 3 C 6 7 2 F 4 C 7 6 3 F 3 5 C 7 6 3 F 3 5 C 7 8 1 F 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE WhensettingSEG3 Standardformode changingCooling Heatingmode WhensettingSEG3 Timerequiredfor modechange Compensationoption forLongpipeorheight diffferencebetween indoorunits Indication andDetails Indication Deta...

Страница 43: ...doffwhentheheatingthermostatisoff e g 2 Setting02seriesSEG15 2 Setting05seriesSEG18 A Roomtemp settemp f heatingcompensationtemp Externalheateristurnedonwhenthetemperatureismaintainedas8 1 F 4 5 C for10minutes Roomtemp settemp f heatingcompensationtemp Externalheateristurnedoffwhenthetemperatureismaintainedas8 1 F 4 5 C 1 8 F 1 C 1 CistheHysteresisforOn Off selection Option SEG13 SEG14 SEG15 SEG16...

Страница 44: ...IBOHJOH B EJHJU PG JOEPPS VOJU JOTUBMMBUJPO PQUJPO TFU UIF 4 BT A Ex When setting the buzzer control into disuse status Note SEG 3 4 5 6 8 9 additional information WhentheSEG3issetas 1 andfollowAutoChangeOverforHRonlyoperation itwilloperateasfollows Cooling HeatingmodecanbechangedwhenThermoOffstatusismaintainedduringthetimewithSEG9 A SetwithSEG4 B SetwithSEG5 C SetwithSEG6 D SetwithSEG8 Cooling Th...

Страница 45: ...ooling heating can be set with the service mode of a wired remote controller Refer to the installation manual of a wired remote controller 2 When using temperature control of discharge air thermo on off of Indoor unit is decided by set room temperature and room temperature and the temperature of discharge air is adjusted to meet the target temperature of discharge air in thermostat On section 3 Wh...

Страница 46: ...dy and safe place Providing information for user X If you turn off the air conditioner when the LED is flickering the LED is also turned off X If you re operate the air conditioner it operates normally at first then detect an error again X When E108 error occurs change the address and reset the system Ex When address of the indoor unit 1 and 2 are set as 5 address of the indoor unit 1 will become ...

Страница 47: ...ion 2 Error due to closed EEV 2nd detection 3 Eva in sensor is detached 4 Eva out sensor is detached 5 Thermal fuse error Open E151 E152 E128 E129 E198 1 COND mid sensor is detached 2 Refrigerant leakage 2nd detection 3 Abnomally high temperature on Cond 2nd detection 4 Low pressure s w 2nd detection 5 Abnomally high temperature on discharged air on outdoor unit 2nd detection 6 Indoor operation st...

Страница 48: ...ththewiredremotecon trolattached WithitsBLDCmotor youcanusesmartadjusttheindoorunitfanspeeddependingontheinstallationcondition Iftheexternalstaticpressureishighsothattheductbecomeslongeroriftheexternalstaticpressureislowsothat theductbecomesshorter UsingtheAutomaticAir Volumefunction thevolumeofexhaustairhasbeenadjusted totheratedvolumeflowrateautomatically Performing the Automatic Air Volume func...

Страница 49: ...ume adjustment is fail Then adjust the fan speed by referring the E S P External Static Pressure setting table t If the coil is not dry run the unit for 2 hours with fan only to dry the coil t The air filter is properly attached into the air passage on the air suction side of the air conditioning unit t Adjust the dampers so that each air inlet and outlet exhusts the designed airflow rate t If usi...

Страница 50: ...0 08 2 010054 1259ED 203434 331110 0 16 4 010054 125E10 203434 331110 AM024FNLD7 0 0 010054 125D2D 204848 331110 0 04 1 010054 125E50 204848 331110 0 08 2 010054 125E50 204848 331110 0 16 4 010054 125E83 204848 331110 AM030FNLD7 0 0 010054 1B5915 205A5A 331110 0 04 1 010054 1B5948 205A5A 331110 0 12 3 010054 1B599F 205A5A 331110 0 24 6 010054 1B5AE4 205A5A 331110 AM036FNLD7 0 0 010054 1B5956 206E6...

Страница 51: ... 1B55D1 201616 331110 010054 1B55E4 201C1C 331110 010054 1B55F2 202323 331110 010054 1B5915 202C2C 331110 010054 1B594A 203535 331110 0 40 SP 0 50 10 SP 12 5 010054 1B5913 201616 331110 010054 1B5917 201C1C 331110 010054 1B5934 202323 331110 010054 1B5968 202C2C 331110 010054 1B599D 203535 331110 0 50 SP 0 60 12 5 SP 15 010054 1B5956 201616 331110 010054 1B595A 201C1C 331110 010054 1B5967 202323 3...

Страница 52: ...10054 13592A 203535 331110 010054 13597E 205252 331110 010054 135AB4 207B7B 331110 0 40 SP 0 50 10 SP 12 5 010054 1B5913 201212 331110 010054 13594C 203535 331110 010054 135AA1 205252 331110 010054 135AF7 207B7B 331110 0 50 SP 0 60 12 5 SP 15 010054 1B5956 201212 331110 010054 135A80 203535 331110 010054 135AE1 205252 331110 010054 135E4A 207B7B 331110 0 60 SP 0 70 15 SP 17 5 010054 135AB3 203535 ...

Страница 53: ... 4 SP 0 50 10 SP 12 5 010054 1E5972 201616 331101 010054 1E5972 201C1C 331101 010054 1E5976 202323 331102 010054 1E598C 202C2C 331103 010054 1E59EC 203535 331104 0 5 SP 0 60 12 5 SP 15 010054 1E59C5 201616 331101 010054 1E59C5 201C1C 331101 010054 1E59CA 202323 331102 010054 1E5AD0 202C2C 331103 010054 1E5E30 203535 331104 Model AM024MNHDCH AM027MNHDCH AM030MNHDCH AM036MNHDCH AM048MNHDCH Static Pr...

Страница 54: ...ontraction tube CAUTION 3 Insert both sides of core wire of the power cable into the connection sleeve f Method 1 Push the core wire into the sleeve from both sides Connection sleeve f Method 2 Twist the wire cores together and push it into the sleeve Connection sleeve 4 Using a crimping tool compress the two points and flip it over and compress another two points in the same location The compress...

Страница 55: ...work is completed wrap it with the insulation tape to finish Insulation tape t In case of extending the electric wire please DO NOT use a round shaped Pressing socket Incomplete wire connections can cause electric shock or a fire WARNING Extending the power cable t Make sure that the connection parts are not exposed to outside t Be sure to use insulation tape and a contraction tube made of approve...

Страница 56: ...55 ENGLISH ...

Страница 57: ...DB68 07187A 00 ...

Отзывы: