22
A
Connecting the refrigerant pipe
1
Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first
manually and then with a torque wrench, a spanner applying the following torque.
Outer Diameter
Torque
mm
inch
/tN
MCGtGU
6.35
1/4
14~18
10.3~13.3
9.52
3/8
34~42
25.1~31.0
12.7
1/2
49~61
36.1~45.0
15.88
5/8
68~82
50.2~60.5
Note
Must apply refrigerant oil on the flaring area to prevent a leak.
2
Be sure that there must be no crack or kink on the bended area.
K
The designs and shape are subject to change according to the model.
A
Liquid refrigerant
port
Gas refrigerant port
Drain hose connection port
A
Gas
refrigerant port
Liquid refrigerant port
Drain hose connection port
AM
77
FNLD
777
AM
77
FNMD
777
/
AM
77
FNHD
777
AM
77
JNMD
777
/
AM
77
JNHD
777
AM
77
JNMP
777
(Drain pump built-in)
Liquid refrigerant port
Gas
refrigerant port
Drain hose connection port
Drain hose connection port
Liquid refrigerant port
Gas refrigerant port
AM
77
MNMD
777
/
AM
77
MNHD
777