35
ENGLISH
Connecting the power terminal
f
Connect the cables to the terminal board using a solderless ring terminal .
f
Properly connect the cables by using certified and rated cables and make sure to fix them properly so that external force
is not applied to the terminal .
f
Use a driver and wrench that can apply the rated torque when tightening the screws on the terminal board .
f
Tighten the terminal screws by applying rated torque value . If the terminal is loose, arc heat may occur and cause fire and
if the terminal is connected too firmly, terminal may get damaged .
Connect one cable per terminal
and fix it with a solderless terminal .
Power cable
Solderless terminal
F1
F2
Terminal name
Tightening Torque
External contact
M3
0 .5 ~ 0 .75 N·m
(0 .37 ~ 0 .55 lbf·ft)
Communication
M3 .5
0 .8 ~ 1 .2 N·m
(0 .59 ~ 0 .89 lbf·ft)
Power
M4
1 .2 ~ 1 .8 N·m
(0 .89 ~ 1 .33 lbf·ft)
<DVM Hydro unit >
1(L)
2(N)
N
L
L
N
<DVM Hydro unit HT>
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 35
DB68-12327A-00_IM_DVM Hydro HT_AA_EN_.indd 35
2023-06-15 오전 10:37:28