How to connect your extended power cables
1 . Prepare the following tools .
Tools
Crimping pliers
Connection sleeve [mm (inch)]
Insulation tape
Contraction tube [mm (inch)]
Spec
MH-14
20 (0 .79) x Φ 6 .5 (0 .26) (H x OD)
Width 19 mm
70 (2 .76) x Φ 8 .0 (0 .31) (L x OD)
Shape
2 . As shown in the figure, peel off the shields from the rubber and wire of
the power cable .
- Peel off 20 mm of cable shields from the pre-installed tube .
• For information about the power cable specifications for indoor
and outdoor units, refer to the installation manual .
• After peeling off cable wires from the pre-installed tube, insert a
contraction tube .
CAUTION
Power cable
20 (0 .8)
20 (0 .8)
60 (2 .4)
120 (4 .7)
180 (7 .1)
20 (0 .8)
180 (7 .1)
120 (4 .7)
60 (2 .4)
20 (0 .8)
20 (0 .8) 20 (0 .8)
Pre-installed tube for the power cable
Unit: mm (inch)
3 . Insert both sides of core wire of the power cable into the connection sleeve .
f
Method 1
Push the core wire into the sleeve from both sides .
Connection sleeve
f
Method 2
Twist the wire cores together and push it into the sleeve .
Connection sleeve
• If cable wires are connected without using connecting sleeves, their contact area becomes reduced, or corrosion
develops on the outer surfaces of the wires (copper wires) over a long time . This may cause an increase of
resistance (reduction of passing current) and consequently may result in a fire .
CAUTION
4 . Using a crimping tool, compress the two points and flip it over and compress another two points in the same location .
- The compression dimension should be 8 .0 mm
2
(0 .0124 inch
2
) .
- After compressing it, pull both sides of the wire to make sure it is firmly pressed .
Compression
dimension
f
Method 1
5 mm (0 .2 inch)
Compress it 4 times .
f
Method 2
5 mm (0 .2 inch)
Compress it 4 times .