13. Installation
Calculating the quantity of refrigerant to add
The quantity of additional refrigerant is variable according to the
installation situation. Thus, make sure the outdoor unit situation
before adding refrigerant.
If you install the excessive length of pipe, add additional
refrigerant as 10g or 20g per unit meter ; refer to the table below.
Refer to the Service Manual for more details on this operation.
Model
Total connecting
pipe length (L)
Adding refrigerant
AJ040TXJ2KG
AJ050TXJ2KG
LT≤30m
Chargeless
AJ052TXJ3KG
AJ068TXJ3KG
LT≤30m
Chargeless
LT≥30m
(LT-30m)x10g
AJ080TXJ4KG
LT≤30m
Chargeless
LT≥30m
(LT-30m)x20g
CAUTION
• The filled-out label must be adhered in the proximity
of the product charging port (e.g. onto the inside of
the stop valve cover).
•
Make sure that the total refrigerant charge does not
exceed (
A
), the maximum refrigerant charge, which
is calculated in the following formula: Maximum
refrigerant charge (
A
)= factory refrigerant charge
(
B
) + maximum additional refrigerant charge due to
piping extension (
C
).
•
Here below, the summary table with refrigerant
charge limits for each products.
(Unit:g)
Model
A
B
C
AJ040TXJ2KG/EU
980
980
0
AJ050TXJ2KG/EU
1180
1180
0
AJ052TXJ3KG/EU
1750
1550
200
AJ068TXJ3KG/EU
2200
2000
200
AJ080TXJ4KG/EU
2800
2000
800
Connecting the drain hose to the outdoor unit
When heating, ice may accumulate. During the process
of defrosting, check if condensation draining is
adequate.
For adequate draining, do the following :
1
Insert the drain plug into the drain hole on the
underside of the outdoor unit.
2
Connect the drain hose to the drain plug.
3
Ensure that condensation draining is adequate.
4
Be sure to plug the rest of drain holes not connected
with drain plugs using drain caps.
Drain cap (3EA)
Drain plug (1EA)
•
When installing the product, make sure that the rack
is not placed under the drain hole.
•
If the product is installed in a region of heavy snow,
allow enough separation distance between the
product and the ground.