309
※ In case you want more information about the controllers and accessories, please refer to the Controller and Accessory TDB
on pvi.Samsung.com site or Global Partner Portal site.
13. Installation
AJ080TXJ4KG
F1 F2 F1 F2
L
N
1(L) 2(N) F1
F2
1(L) 2(N) F1
1(L) 2(N) F1
1(L) 2(N) F1
F2
1 2
1 2
F1 F2
F1 F2
1 2
2
1
F2
1 2
F1 F2
F1 F2
F2
F1 F2
F1 F2
1 2
2
1
1 2
1
2
B
C
B
C
B
C
B
C
A
1(L) 2(N) 1(L) 2(N)
F1 F2
F1 F2
A-unit
B-unit
C-unit
D-unit
Indoor unit
Assembly cable
Earth
terminal
Earth
terminal
Outdoor unit
Main Power
Supply cable
Power cable to indoor units
Communication cable
to indoor units
A
B
C
Cable Type : A
Cable Type : B
Cable Type : C
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Specification for circuit breaker and power supply cord
•
Power supply cord is not supplied with air conditioner.
•
Select the power supply cord in accordance with relevant local and national regulations.
•
Wire size must comply with the applicable local and national code.
• Specifications for local wiring power supply cord and branch wiring are in compliance with local cord.
Model
Outdoor Units
Maximum Input Current[A]
Power Supply
Rated
Outdoor
Indoor(Max.)
Total
MCA
MFA
Outdoor Unit
Indoor Unit
Hz
Volts
AJ040TXJ2KG
2 Room
50
1phase,220-240
8.5
0.8
9.3
9.30
10.63
AJ050TXJ2KG
2 Room
50
1phase,220-240
11.0
0.8
11.8
11.80
13.75
AJ052TXJ3KG
3 Room
50
1phase,220-240
11.0
1.2
12.2
12.20
13.75
AJ068TXJ3KG
3 Room
50
1phase,220-240
16.6
1.2
17.8
17.80
20.75
AJ080TXJ4KG
4 Room
50
1phase,220-240
16.6
1.6
18.2
18.20
20.75
NOTE
1. Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F , IEC:60245 IEC 66 / CENELEC: H07RN-F )
2. Select power supply cord based on MCA.
3. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
4. MCA represents maximum input current.
5. MFA represents capacity which may accept MCA.
Abbreviations
- MCA : Min. Circuit Amps. (A)
- MFA : Max. Fuse Amps. (A)
Screw
Tighten Torque(kgf.cm)
Position
M4
12.0~18.0
1(L),2(L),L,N,F1,F2