Indoor units address SW setting correct, but outdoor unit’s PCB displayed E201 Error Code.
Check point
Remarks
Indoor unit’s sub PCB address SW or sub PCB is
connected by mistake.
Check to indoor unit’s sub PCB wire connecting
condition.(misconnecting or Sub PCB is out of order)
Indoor
Sub PCB
Address setting mode change to auto address setting.
Following auto address setting steps.
Manual Address setting is Option in FJM PLUS A.
But we solved problem like this situation, with auto address setting.
Q1
Analysis
Step 1
Step 2
Step 3
Guidance
Contents
When the pipe checking operation is finished, outdoor sub PCB display E190 Error code.
Check point
Remarks
Outdoor unit fails to search indoor units or to check
indoor address.
The pipe checking operation
Whether The gas and liquid pipes are crossed with
each other, check to connecting.
Pipe connecting
Check to outdoor unit’s EEV coil being connected in
proper location.
EEV Coil
Check to indoor unit’s sensor being connected in
proper location.
Indoor sensor
During the pipe checking operation , system check temperature change of indoor Heat exchanger.In case, indoor
sensor defect, EEV coil connector detach, malfunction of EEV, Leakage of Refrigerant, and etc can make this case.
- Address setting another case
Q1
Analysis
Step 1
Step 2
Guidance
Contents
When the system installation is finished, outdoor unit’s PCB display E202 Error code.
Check point
Remarks
This problem is caused by outdoor unit’s communication
part trouble or indoor units power and communication
line trouble.
The pipe checking operation
Check to connect outdoor unit and indoor units cable.
Pipe connecting
Replace outdoor unit’s ass’y control or indoor unit’s
ass’y control.
EEV Coil
Basically, This error caused by communication between Indoor Units and Outdoor Unit.
First of all, check the all communication connection and PCB’s status.
Содержание AJ007JNADCH
Страница 17: ...Samsung Electronics 3 1 3 Disassembly and Reassembly Necessary Tools Item Remark SCREW DRIVER MONKEY SPANNER ...
Страница 54: ...3 38 Samsung Electronics MEMO ...
Страница 100: ...6 4 Samsung Electronics 6 2 OUTDOOR UNIT Q AJ020JCJ2CH AJ024JCJ3CH ...
Страница 101: ...Samsung Electronics 6 5 Q AJ036JCJ5CH ...
Страница 102: ...6 6 Samsung Electronics MEMO ...
Страница 111: ...Samsung Electronics 7 9 AJ020JCJ2CH CYCLE DIAGRAM 7 8 Refrigerating Cycle Diagram AJ024JCJ3CH CYCLE DIAGRAM ...
Страница 112: ...7 10 Samsung Electronics AJ036JCJ5CH CYCLE DIAGRAM ...