Installation Procedure
English
External Static Pressure
External Static
Pressure (mmAq)
1.0
2.0
3.0
4.0
AJ026RBLDEG 015201-1400FB 015201-14020C 015201-140360 015201-1403A2
AJ035RBLDEG 015201-16025D 015201-16026E 015201-1603C4 015203-160108
External Static
Pressure (mmAq)
0.0
2.0
4.0
6.0
AJ052RBMDEG 012221-194247 012221-194360 012221-1943A2 012223-194105
•
Mark ‘
’ is the basic model of this product.
Refer to the table above depending on the installation
environment.
Step 15 Setting the Indoor unit
addresses
1
Before installing the indoor unit,assign an address to the
indoor unit according to the air conditioning system plan.
2
The address of the indoor unit is assigned by adjusting
MAIN(SW02) switch.
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10K11 K12
3
The MAIN address is for communication between the
indoor unit and the outdoor unit. Therefore, you must set
it to operate the air conditioner properly.
4
It is required to set the RMC address if you install the wired
remote controller and/or the centralized controller.
5
If you install optional accessories such as the wired
remote controller, centralized controller, etc. see an
appropriate installation manual.
6
If an optional accessory is not installed, you do not have
to set the RMC address. However, adjust K1 and K2
switches of the SW05 DIP switch to “ON” position in this
case.
7
Set the MAIN address by adjusting the rotary
switch(SW02) from 0 to 9. Each indoor unit connected to
the same outdoor unit must have different address.
Step 16 Additional Functions
NO.
Function
ON
OFF
SW05
K1
External room sensor
Not use
Use
K2
Centralized controller
Not use
Use
K3
Compensate RPM
Standard
Up
K4
Drain Pump
Not use
Use
•
K1 OFF
Heating mode : Setting temperature compensation
value = 0°C
Thermo OFF
Fan OFF
NO.
Function
ON
OFF
SW06
K5
Indoor Temperature
Compensation for Heating Mode
+2°C
+5°C
K6
Filter Time
1,000
hours
2,000
hours
K7
Hot Water Coil
Not Use
Use
K8
-
-
-
NO.
Function
ON
OFF
SW07
K9
-
-
-
K10
-
-
-
K11
External control
Not Use
Use
K12
External Control Output
Thermal ON Operation ON
SW05
SW06
SW07
Ins
tallation Pr
oc
edur
e
20