Installation Procedure
Ins
tallation Pr
oc
edur
e
English
Without the drain pump
1
Install horizontal drainpipe with a slope of 1/100 or
more and fix it by hanger space of 1.0~1.5m.
1
Install U-trap at the end of the drainpipe to prevent a
nasty smell to reach the indoor unit.
2
Do not install the drainpipe to upward position. It may
cause water flow back to the unit.
1~1.5m
Horizontal drainpipe
more than 1/100 slope
Ceiling
Hanger
Flexible hose
With the drain pump
1
The drain pipe should be installed within 300mm to
550mm from the flexible hose and then lift down 20mm
or more.
2
Install horizontal drainpipe with a slope of 1/100 or
more and fix it by hanger space of 1.0~1.5m.
3
Install the air vent in the horizontal drainpipe to prevent
water flow back to the indoor unit.
NOTE
• You may not need to install it if there were proper
slope in the horizontal drainpipe.
4
The flexible hose should not be installed upward
position, it may cause water flow back to the indoor unit.
1~1.5m
20mm
or more
200mm
or more
Hanger
Within
300~550mm
Air vent
300mm or less
Flexible hose
Horizontal drainpipe
more than 1/100 slope
Ceiling
Step 11 Performing the drainage test
Prepare a little water about 2 liter.
1
Pour water into the base pan in the indoor unit as shown
in figure.
2
Confirm that the water flows out through the drain hose.
Step 12 Connecting the power and
communication cables
CAUTION
• Always remember to connect the refrigerant pipes
before performing the electric connections. When
disconnecting the system, always disconnect the electric
cables before disconnecting the refrigerant pipes.
• For the product that uses the R-32 refrigerant, be
cautious not to generate a spark by keeping the
following requirements:
– Do not remove the fuses with power on.
– Do not disconnect the power plug from the wall outlet
with power on.
– It is recommended to locate the outlet in a high position.
• Always remember to connect the air conditioner to the
grounding system before performing the electric connections.
Use a crimp ring terminal at the end of each wire.
The indoor unit is powered through the outdoor unit by
means of a H07 RN-F connection cable (or a more power
model), with insulation in synthetic rubber and a jacket
in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.
1
Remove the screw on the electrical component box and
remove the cover plate.
2
Route the connection cord through the side of the indoor
unit and connect the cable to the terminals refer to the
figure below.
3
Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
4
Reassemble the electrical component box cover, carefully
tightening the screw.