Installing the air conditioner
Fixing and insulating the connection part of the pipe
f
Check the leakage on the connection part of pipes and make sure the
insulated them afterwards. Pipe must be insulated properly so that
condensation does not form.
f
Use foamed polyethylene with thickness over 5 mm to insulate the
connection part of pipe.
High pressure
pipe
Low pressure
pipe
f
When you insulate the pipe connection part, make sure
that overlapping part of the insulator is over 30 mm.
30 mm or
ove
r
Insulator for pipe
connection part
Pipe insulation
f
Fix the pipe with a clamp and screws.
WARNING
f
Cut the middle part of the pipe outlet protection rubber before connecting the pipe.
ENGLISH-54