• Please use rated wires or products (with heat resistance over 105 °C) of all the wires and the switches or fuses in
the cabinet panel. (Retailer and installer is responsible for the use of parts that does not meet the wire standards
or capacity requirements)
• Make sure that wires doesn’t make any sparks around the auxiliary power switch or installed in a place with
high temperature. (If the ambient temperature is high, allowable current of the wire will decrease and current
reduction factor will occur.)
• Please install the auxiliary power switch in a dry place and install panel board or electrical component box.
• Please install circuit breaker in the panel board.
• When connecting the main power, press the wire to the terminal to secure connection.
• Selecting crimp-style ring terminal
Silver solder
AF30/50HV Series
Thickness of the wire (mm
2
)
B (mm)
d2 (mm)
2.5
9.5 and below
4.5 and over
4
9.5 and below
4.5 and over
6
-
-
AF30HV Series
Usable voltage range for 220 - 240 V
198 V ~ 242 V
AF50HV Series
Usable voltage range for 380 - 415 V
342 V ~ 418 V