Troubleshooting
Samsung Electronics
51
4-4-2 Troubleshooting for outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and IN
V
ERTER PCB
.
No.
LED Display
Displayed
P
CB Assy
Meaning
Remarks
Error Code
Red
Green
Yellow
-
z
|
MAIN/IN
V
ERTER
Normal operation
(MAIN
:
Indoor
¥
Outdoor
:
G
reen ON)
(IN
V
ERTER
:
MAIN PCB
¥
IN
V
ERTER PCB
:
G
reen ON)
-
1
z
|
MAIN
Control Kit quantity is mismatched
.
Check Control Kit quantity
setting in outdoor
E201
2
z
z
|
MAIN/IN
V
ERTER
Abnormal state, no communication between
Indoor and Outdoor Main PCB
Check electrical
connection and setting
E202
|
|
4
z
z
MAIN/IN
V
ERTER
1min
.
Time out of communcation
error(Main
¥
Inverter)
Check electrical
connection and setting
E203
5
z
|
MAIN
Outdoor temp sensor error
Check Outdoor sensor
Open/Short
E221
6
z
|
MAIN
Cond
.
temp sensor error
Check Cond
.
sensor
Open/Short
E231
7
z
|
MAIN
Discharge temp sensor error
Check Discharge sensor
Open/Short
E251
8
z
|
MAIN
OLP Sensor Error
Check OLP sensor
Open/Short
E320
9
z
|
MAIN
Detection of Outdoor Freezing when Comp
.
Stop
Check Outdoor Cond
.
E403
10
z
|
MAIN
Protection of Outdoor Overload when Comp
.
Stop
Check Comp
.
when it start
E404
11
z
|
MAIN
Discharge temperature of a compressor in an
outdoor unit is overheated
.
E416
12
z
|
MAIN
Outdoor EE
V
Open error
Check EE
V
E419
13
z
|
MAIN
Miss wiring error at
3Phase power source line
(Only 3Phase Model)
Check Power
Line-R,S,T,N
E425
14
z
|
MAIN
G
as leakage error
(Stop state)
Check
G
as leak
E439
15
z
|
MAIN
Heating operation is not available since the
outdoor air temperature is over 35°C
.
Heating
E440
16 Cooling
E441
16
z
|
MAIN
G
as leakage error
(Before operating)
Check
G
as leak
E443
17
|
|
z
MAIN/IN
V
ERTER
Outdoor unit BLDC Fan 1 or Fan 2 error
FAN1 error
E458
19 E475
18
|
|
MAIN/IN
V
ERTER
Comp
.
Starting error
E461
19
z
|
MAIN
Primary Current Trip error
E462
20
z
|
MAIN
Over current trip / PFC over current error
Check OLP sensor
E463
21
|
|
MAIN/IN
V
ERTER
IPM(I
G
BT Module) Over Current(O
.
C)
E464
22
|
z
MAIN/IN
V
ERTER
Comp
.
Over load error
E465
23
z
|
MAIN/IN
V
ERTER
DC-Link voltage under/over error
Check AC Power or
DC_Link voltage
E466
|
Off
Blink
z
On
RC160MHXGA_SM_E_34513A(1)_4.indd 51