ENGLISH-17
02
INST
ALL
ATION
C
o
nnecting the cable
P
o
wer cable speci
fi
cati
o
ns
1 phase
Outd
oo
r unit
Rated
V
o
ltage Range
MCA
MFA
Hz
V
o
lts
Min
Max
Min. Circuit Amps.
Max. Fuse Amps.
AE090JXEDEH
50
220-240
198
264
22 A
27.5 A
AE120JXEDEH
50
220-240
198
264
28 A
35 A
AE140JXEDEH
50
220-240
198
264
30 A
37.5 A
AE160JXEDEH
50
220-240
198
264
32 A
40 A
f
The power cable is not supplied with Air to Water Heat pump.
f
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
fl
exible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
f
This Equipment complies with IEC 61000-3-12.
3 Phase
Outd
oo
r unit
Rated
V
o
ltage Range
MCA
MFA
Hz
V
o
lts
Min
Max
Min. Circuit Amps.
Max. Fuse Amps.
AE090JXEDGH
50
380-415
342
457
10 A
16.1 A
AE120JXEDGH
50
380-415
342
457
10 A
16.1 A
AE140JXEDGH
50
380-415
342
457
11 A
16.1 A
AE160JXEDGH
50
380-415
342
457
12 A
16.1 A
f
The power cable is not supplied with Air to Water Heat pump.
f
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
fl
exible cord (Code
designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
f
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
3.3[MVA] at the interface point between the user's supply and the public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 3.3[MVA].