Field setting mode
52
English
52
English
AD
VANCED OPERA
TION
Economic DHW Heating
•
DHW heating only by the heat pump to save energy. Target DHW temperature is lower than the temperature
set by user. The temperature difference is defined by FSV #5021. (default: 5°C)
–
If user sets the temperature 45°C, the system sets the target temperature 40°C with the default
setting.
Peak Power Control
•
If users make contracts with local electric power company for limiting the amount of power consumption
when a surge in power usage, users can set FSV of “Forced off”.
•
According to FSV (#5041), Default is Non-usage. And According to FSV (#5042), If input is “0 (default)”, Back up
heater (BUH) is unavailable while external contact is high.
If input is “ 1”, Only Compressor(Heat Pump) is available.
If input is “ 2”, Only Booster Heater (BSH) is available.
If input is “3”, nothing is available.
•
Applying the control when power voltage of input contact is high is default. According to FSV (#5043), it is
available to adopt this logic in low condition exceptionally.
•
When applying to this logic, SAMSUNG controller come to get “Thermo off” condition for all operation.
•
If not used for a long time, anti-freeze fluid shall be used for preventing damage to the unit in cold condition.
TDM (Time-Division Multi) Variables (TDM product Only)
•
Please refer to the page 27.
Power peak control for Smart Grid
[D-00]
Compressor
Back up heater
Booster heater
0 (Default)
Permitted
Forced off
Permitted
1
Permitted
Forced off
Forced off
2
Forced off
Forced off
Permitted
3
Forced off
Forced off
Forced off