AD
VANCED OPERA
TION
Field Setting Value
Main Menu &
Code
Sub Menu
Function
Description
Sub
Code Default
Min
Max
Step
Unit
Others Code
50∗∗
Outing
Auto Cooling WL1 Temp
∗∗15
25
5
25
1
˚C
Auto Cooling WL2 Temp
∗∗16
25
5
25
1
˚C
Auto Heating WL1 Temp
∗∗17
15
15
55
1
˚C
Auto Heating WL2 Temp
∗∗18
15
15
55
1
˚C
Target Tank Temp
∗∗19
30
30
70
1
˚C
DHW Saving Mode
Temp Difference
∗∗21
5
0
40
1
˚C
TDM Variable
(TDM product Only)
Priority Max. Operation
Time
∗∗31
30
10
90
5
min
Non Priority Min. Operation
Time
∗∗32
5
3
60
1
min
A2A / DHW Priority
∗∗33
0
0 (A2A) 1 (DHW)
1
-
Power Peak
Control
Application
∗∗41
0 (No)
0
1 (Yes)
-
-
Select forced off parts
∗∗42
0 (All)
0
3
1
-
Using input voltage
∗∗43
1 (High) 0 (Low)
1
-
-
Frequency Ratio Control
∗∗51
0 (No)
0
1 (Yes)
-
Remote Controller Setting Range : Code 10∗∗
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub
Code
Default
Min
Max
Step
Unit
Remote
Controller
Setting Range
Code 10∗∗
Water Out Temp for
Cooling
Max
∗∗11
25
18
25
1
˚C
Min
∗∗12
16
5
18
1
˚C
Room Temp for Cooling
Max
∗∗21
30
28
30
1
˚C
Min
∗∗22
18
18
28
1
˚C
Water Out Temp for
Heating
Max
∗∗31
55
37
55
1
˚C
Min
∗∗32
25
15
37
1
˚C
Room Temp for heating
Max
∗∗41
30
18
30
1
˚C
Min
∗∗42
16
16
18
1
˚C
DHW Tank Temp
Max
∗∗51
50
50
70
1
˚C
Min
∗∗52
40
30
40
1
˚C