Troubleshooting
76
Samsung Electronics
Error mode
Contents
Measure
Product operation in
error condition
Error type
Outdoor unit/
Compressor/Indoor
unit
Gas leak error
Check the coolant charging status
Check the indoor EVA sensor.
Check if the outdoor unit service value is open.
Check that the indoor/outdoor installation pipe/wiring
are correct.
Operation Off
Self diagnostic
error
Inverter EEPROM loading error Check EEPROM DATA.
Check the normal operation of PCB.
Operation Off
Comp down
error
Communication error between
the Hydro Unit and wired
remote controller
Check the Indoor unit PBA and wired remote controller .
Operation Off
communication
error
Wired remote communication
error
Communication tracking error between the CONTROL
KIT and wired remote controller.
Operation Off
Wired Remote
Controller
Wired remote controller
temp sensor SHORT or OPEN
Check sensor connection status.
Operation Off
wired remote
controller
sensor error
Memory(EEPROM) Read
Write error(Wired remote
controller data error)
Check the wired remote controller .
Operation Off
communication
error
Zone 1 water-out temperature
sensor error
Short- or open-circuit error of the Zone 1 water-out
temperature sensor.
Operation Off
Indoor Unit
error
Zone 2 water-out temperature
sensor error
Short- or open-circuit error of the Zone 2 water-out
temperature sensor.
Operation Off
Indoor Unit
error
Water inlet (PHE) temperature
sensor error
Refer to details.
Water outlet (PHE)
temperature sensor error
Refer to details.
Water outlet (backup heater)
temperature sensor error.
Refer to details.
DHW tank temperature sensor
error
Refer to details.
Refrigerant gas inlet (PHE)
temperature sensor
Refer to details.
Low flow rate error
Refer to details.
Normal flow rate error
Refer to details.
Thermostat wrong connection
error
Check the wiring of Hydro Unit Thermostat.
Check the Cooling /Heating signal : Concurrent wiring or
not.
Operation Off
Indoor sensor
error
Mixing Valve Outlet
temperature sensor error
Refer to details.
Error for disinfection operation
Error that the set temperature for disinfection operation
is not reached, or, after reaching, the temperature fails to
continue for the requested time.
-
Indoor Unit
error
Wired remote controller (cont.)
Содержание AE050RXYDEG
Страница 25: ...Disassembly and Reassembly 28 Samsung Electronics No Parts Procedure Remark ...
Страница 51: ...Disassembly and Reassembly 54 Samsung Electronics No Parts Procedure Remark ...
Страница 64: ...Disassembly and Reassembly Samsung Electronics 67 No Parts Procedure Remark ...
Страница 111: ...Wiring Diagram 114 Samsung Electronics This Document can not be used without Samsung s authorization 6 1 2 1Phase Model ...