Troubleshooting
Samsung Electronics
95
4-5-9 GAS leak error(E554)
1. Check items
1) Is refrigerant charged?
2) Is the evaporator sensor of indoor unit connected correctly?
2. Check procedure
Does the error occur?
Yes
No
Normal operation
Yes
No
Are the service valves fully opened?
Yes
No
Open the service valves
Is the evaporator sensor of
indoor unit connected correctly?
Yes
No
Connect the sensor’s connector
Yes
No
Charge refrigerant
Is the value of resistance
between each phase(*) for compressor
smaller than 2
Ω?
Exchange the compressor
(*) U
↔
V, V
↔
W, W
↔
U
Is refrigerant charged?
Exchange INVERTER PCB
Содержание AE050RXYDEG
Страница 25: ...Disassembly and Reassembly 28 Samsung Electronics No Parts Procedure Remark ...
Страница 51: ...Disassembly and Reassembly 54 Samsung Electronics No Parts Procedure Remark ...
Страница 64: ...Disassembly and Reassembly Samsung Electronics 67 No Parts Procedure Remark ...
Страница 111: ...Wiring Diagram 114 Samsung Electronics This Document can not be used without Samsung s authorization 6 1 2 1Phase Model ...