Safety Zone
WARNING
• In case of a leakage the refrigerant must not be able to enter
the indoor under any circumstances.
The Safety Zone shall not have any building openings such as:
Windows, Doors, Light wells, Flat roof windows, Air Inlet /
Outlet of ventilation systems, etc.
• R-290 refrigerant is heavier than air and can be collected on
the ground. There should be no sinking or deepening of the
ground in the safety zone.
• The safety zone should not extend to intact buildings or public
spaces.
• The safety zone cannot be modified later to violate the
protection rules.
(Unit : mm)
1,000
1,000
1,000
500
1,000
500
500
500
300
1,000
500
1,000
1,000
500
• When installed on the ground
• When installed in a place with
a flat roof
• When installed on the ground in
front of a building wall
2,300
300
500
600
500
1,000
500
300
300
2,300
500
500
1,000
• When installed at the right
corner of a building
• When installed at the Left corner
of a building
When installing 1 outdoor unit
(Unit : mm)
300 or more
1,500 or more
• Wall on suction-side
• When the air outlet is towards
the wall
1,500 or more
2,300 or more
600 or
mor
e
300 or more
• Top-side obstacle
• Discharge-side obstacle
• Wall on discharge-side
• Top-side obstacle
• Wall on suction-side
1,500 or more
300 or more
• Suction-side obstacle
• Wall on discharge-side