Electrical installation

English

El

ectric

al

 instal

lation

Electrical installation

Electrical installation

Precautions when connecting the 

electrical wiring

  WARNING

•  Make sure first the water piping is connected before the 

electrical wiring work.

•  When removing or relocating the equipment, power off 

first and then disconnect the electrical wiring.

•  Connect the air to water heat pump to a protected earth 

(PE) before connecting the phase and neutral to the 

product.

•  Follow the local installation standards and regulations 

when installing electrical wiring.  

Electrical wiring should be installed by a certified 

electrician or certified installer. Failing to comply, might 

lead to damaging the product, starting a fire and personal 

injury, electrocution or death.

•  Make sure that wiring work must be done by an authorized 

electrician. 

The wiring materials and wiring work must comply with the 

applicable legislation.

•  Always verify that a suitable grounding connection is available.
•  Verify that the voltage and frequency of the power supply 

comply with the specifications and that the installed power 

is sufficient to ensure the operation of any other domestic 

appliance connected to the same electric lines.

•  Always verify that the cut-off and protection switches are 

suitably dimensioned.

•  Verify that the air to water heat pump is connected to the 

power supply in accordance with the instructions provided in 

the wiring diagram included in the manual.

•  Always verify that electric connections (cable entry, the section 

of leads, protections…) comply with the electric specifications, 

local regulations and installation standards and with the 

instructions provided in the wiring scheme. 

Always verify that all connections comply with the standards 

applicable to the installation of air to water heat pumps.

•  Depending on the condition of power supply, unstable power or 

voltage may cause malfunction of the parts or control system. 

(Avoid using power supply from an electric generator, like on 

a ship etc).

  CAUTION

•  Make sure that you earth the cables.

 

– Do not connect the earth wire to the gas pipe, water 

pipe, lighting rod or telephone wire. If earthing is not 

complete, electric shock or fire may occur.

•  Install the circuit breaker.

 

– Failing to install a circuit breaking device may result in 

electric shock and fire occurrence.

•  Install the power cable and communication cable of the 

indoor and outdoor unit according to IEC 60364-1 (Electrical 

installations and protection against electric shock).

•  Be sure to install both an earth leakage detector and circuit 

breaker with specified capacity in accordance with relevant 

local and national regulations.

 

– If it is not installed properly, it may cause electric 

shocks and fire.

Electrical wiring diagram

Communication Cable

   

Power Supply

MCCB+ELB 

or 

RCBO(ELCB)

Power Supply

MCCB+ELB 

or 

RCBO(ELCB)

Specification of power cable

• 

1 Phase

 

– The power cables are not supplied with the air to water 

heat pump.

 

– Power supply cords of parts of appliances for outdoor 

use shall not be thinner than polychloroprene sheathed 

flexible cord (Code designation IEC:60245 IEC 57 / 

CENELEC:H05RN-F)

 

This equipment complies with IEC 61000-3-12.

Outdoor unit

Rated

Voltage Range

MCA

MFA

Hz

Volts

Min

Max

Min 

Circuit 

Amps.

Max

 

Fuse 

Amps.

AE050CXYDEK 50 220-240 198

264

16.1

17.6

AE080CXYDEK 50 220-240 198

264

26

28.6

AE120CXYDEK 50 220-240 198

264

32

35.2

AE160CXYDEK

50 220-240 198

264

32

35.2

• 

3 Phase

 

– The power cables are not supplied with the air to water 

heat pump.

 

– Power supply cords of parts of appliances for outdoor 

use shall not be lighter than polychloroprene sheathed 

flexible cord (Code designation IEC:60245 IEC 66 / 

CENELEC:H07RN-F)

 

This equipment complies with IEC 61000-3-12 provided 

that the short-circuit power (SSC) is greater than or equal 

to 3.3[MVA] at the interface point between the user’s 

supply and the public system. It is the responsibility of 

the installer to ensure, by consultation with the energy 

company if necessary, that the equipment is connected 

only to a supply with a short-circuit power (SSC) greater 

than or equal to 3.3[MVA].

Outdoor unit

Rated

Voltage Range

MCA

MFA

Hz

Volts

Min

Max

Min 

Circuit 

Amps.

Max

 

Fuse 

Amps.

AE080CXYDGK 50 380-415 342

457

16.1

17.7

AE120CXYDGK 50 380-415 342

457

16.1

17.7

AE160CXYDGK

50 380-415 342

457

16.1

17.7

Содержание AE CXYD Series

Страница 1: ...WaterHeatPump Installation manual EHS Mono Outdoor Unit AE CXYD Thank you for purchasing this Samsung product Before operating this unit please read this manual carefully and retain it for future refe...

Страница 2: ...14 Connecting the water pipes 14 Water Charging 14 Setting capacity and pre pressure of the expansion vessel 15 Protection of the water circuit freezing 15 Outdoorwater piping insulation 17 Minimum a...

Страница 3: ...uman health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users s...

Страница 4: ...unit Neversit orstand on the product All the materials used forthe manufacturing and packaging of the airto waterheat pump are recyclable The packing material and exhausted batteries of the remote con...

Страница 5: ...ng flammable refrigerants Safety checks are required to minimize the ignition risk for servicing the units containing flammable refrigerants Servicing shall be performed following the controlled proce...

Страница 6: ...the recovery units orcylinders If compressors orcompressoroils are to be removed make sure that they have been evacuated to the acceptable level to ensure that flammable refrigerant does not remain in...

Страница 7: ...product in the protective packaging and keep covered until final installation Preparation of both horizontal and vertical transport routes and equipment might be required in orderto get the product i...

Страница 8: ...d does not generate any unnecessary noise and vibration Position the outdoorunit so that the airflows directly towards the open area Place the outdoorunit where there are no plants and animals because...

Страница 9: ...d laterto violate the protection rules Unit mm 1 000 1 000 1 000 500 1 000 500 500 500 300 1 000 500 1 000 1 000 500 When installed on the ground When installed in a place with a flat roof When instal...

Страница 10: ...and serviceable undersafe working conditions forpeople orthings Installing the unit at a locationwith strong winds Outdoorunit must be fixed firmly so that it can withstand the wind speed of the stro...

Страница 11: ...lean it with waterto remove attached salinity 6 If the protective coating orgalvanised steel of the product is damaged during the installation ormaintenance make sure to repairit 7 Check the condition...

Страница 12: ...tions Woodenpallet Forklift 1 050mm NOTE When looking at the product from the front there is a centerof gravity right from the middle of the product Referto the centerof gravity mark attached to the p...

Страница 13: ...runs away correctly and safely 150mm WARNING If the drainage is not adequate it can lead to stagnant water and ice build up causing system performance issues and possible damages Drainhole 20 Drainpl...

Страница 14: ...ench as specified in the below table If not connections and parts can be damaged and leak The unit is only to be used in a closed watersystem If applications are in open watercircuit it will generate...

Страница 15: ...the installation the installation height is considered 0m When Expansion vessel has a capacity 8 liters and1bar pre charged Watervolume of total system forreliable performance is minimum 30 Liter AE0...

Страница 16: ...raturevalue When using the EHS forcooling in the summertime an anti freeze valvewith ambient sensoris required to avoid unwanted opening due to lowwatertemperatures To protect the field piping against...

Страница 17: ...m Minimum insulation thickness mm 20 19 20 30 32 30 40 40 40 50 50 NOTE This recommendation ensures good operation of the unit however local regulations may differand shall be followed Minimum activew...

Страница 18: ...ct the earth wire to the gas pipe water pipe lighting rod ortelephone wire If earthing is not complete electric shock orfire may occur Install the circuit breaker Failing to install a circuit breaking...

Страница 19: ...t and route them through the factory mounted cable sleeves into the switch box Powerand communication cable configuration Powersupply cable must be guided through the knock out hole on the bottom righ...

Страница 20: ...itchwithinyourarm s reach that disconnects all poles with contact gap of a least 3 mm Route the cable through the frame Connect the wires to the terminal block and fix the cable with the cable tie R S...

Страница 21: ...the selected options press and hold the K2 switch for2 seconds to store the value The changed value of the option will be saved when the entire segment display blinks and tracking mode begins CAUTION...

Страница 22: ...K 2 BLANK 1 3 times InverterFault Detection Comp 1 K 3 I 1 4 times End Key operation K2 Numberof Press KEY operation 7 segment display 1 time Trial operation in Cooling mode K 4 BLANK BLANK 2 times Di...

Страница 23: ...nd on this manual the factory refrigerant charge of the product the additional refrigerant amount charged in the field Unit kg tCO e a b DO NOTCHARGE Refrigerant type GWPvalue R 290 3 GWP Global Warmi...

Страница 24: ...e Error Detect when the system is not operated OUTDOOR UNIT E440 Forbid Heat mode Operation when OutdoorTemperature is over43 C OUTDOOR UNIT E441 Forbid Cooling Mode when Outdoor Temperature is Low10...

Страница 25: ...T_CT Thermistor CompressorTop T_D Thermistor Discharge pipe T_EI Thermistor EVI In T_EO Thermistor EVI Out T_II Thermistor Heat ExchangerIn T_S Thermistor Suction pipe T_WI Thermistor WaterIn T_WO The...

Страница 26: ...HE Part Description CV Check Valve COMP Compressor HX_IC Heat Exchanger Intercooler HX_M Heat Exchanger Main Outdoorunit HX_PHE Heat Exchanger PHE IPMC IPM Cooler OFM OutdoorFan Motor AC Accumulator P...

Страница 27: ...with the higher set temperature to Zone 2 d A ir vent included in tank integrated hydro unit In case that the water piping would be located in a higher position than the air vent of the tank integrate...

Страница 28: ...essel Decoupler Safety group Safetyvalve Manometer Expansion vessel 3waymixingvalveforfloorheating incaseofcombinationwithradiators Mixing valve temperature sensorb Vibro isolating mounting bases Symb...

Страница 29: ......

Страница 30: ...This appliance is filledwith R 290 A3...

Отзывы: