12
Unit installation
English
Unit instal
lation
Moving the outdoor unit
• Be sure that the moving route is safe by anticipating the
weight of the outdoor unit in advance.
•
Do not slant the product more than 30˚when carrying it.
(always keeping the unit upright)
• The surface of the heat exchanger is sharp. Be careful not to be
injured while moving and installing by wearing your personal
protective equipment (gloves, etc.).
Moving the outdoor unit by hoisting
• Only hoist the product with using approved lifting straps
(according to local regulations). Keep long straps to avoid
damage to the panels. Always wear personal protective
equipment (safety helmet) when hoisting.
Lifting straps
Plate protection cloth
Moving the outdoor unit with a forklift
• Insert the fork into the wooden pallet at the bottom of the
outdoor unit carefully. Be careful that the fork does not
damage the outdoor unit. Operating a forklift may require
special certification or training according to local regulations.
Wooden pallet
Fork lift
1,050 mm
NOTE
• When looking at the product from the front, there is a center of
gravity right from the middle of the product.
Refer to the center of gravity mark attached to the product.
Mounting the outdoor unit
The outdoor unit must be installed on a rigid and stable base to
avoid any increase in the noise level and vibration, particularly if
the outdoor unit is to be installed in a location exposed to strong
winds or at a height, the unit must be fixed to an appropriate
support (wall or ground).
CAUTION
• When tightening the anchor bolt, tighten the rubber washer to
prevent the outdoor unit bolt connection part from corroding.
• Make a drain outlet around the base for outdoor unit drainage.
• If the outdoor unit is installed on the roof, you have to check
the ceiling strength and waterproof the unit.
• The anchor bolt must be 20 mm or higher from the base
surface.
※
In order to prevent freezing of water drains, additional
protection such as application of a heating cable may be
required.
4 x M12
620 mm
344 mm
Outdoor unit support
Outdoor unit
4 x M12
Anchor bolt
20 mm
Designed to cut off residual vibration
from outdoor unit to rack.
(not supplied with product)
Base surface