Troubleshooting
4-50
4-4-19. DC LINK over-current / low-voltage error (Error Code : E466)
H/W DC_Link Over Voltage Error (Error Code : E483)
AC Input Voltage Sensor Error (Error Code : E488
1. Test
items
1) Check the power connection. / Check the restart after power reset.
ĺ
Is there a fault in input power? (Single-phase : 220Vac, 3-phase : 380Vac)
ĺ
Does error occur again at operation after power is reset?
2) Check the connection of the power, and check whether the jointed power connection exists.
ĺ
After having installed several units, please check that communication wires are not interchanged with piping.
3) Check the reactor and its connecting wires.
4) Check the fuses of EMI PBA.
5) Check the Terminal Block and Power Terminal Box and the wire assembly.
2. Check
procedure
Yes
Reconnect the power wire.
No
Is the power wire correctly connected?
1.Check the connecting wires. (between the
reactor wire and the Inverter PCB wire of the
outdoor unit)
ĺ
Check the normal operation.
ĺ
End the service
2. Replace the reactor.
ĺ
Check the normal
operation.
ĺ
End the service.
No
Power OFF
Yes
Check the
reactor and its connecting wires.
1. Is the wire between the reactor and the
Inverter PCB of the outdoor unit correctlyconnected?
2. Is there any fault such as scratch,
pressing, broken or
loosened
terminal?
1. Fasten the screws between Terminal Block and
power wire.
ĺ
Check the normal operation.
ĺ
End the service.
2. Connect the terminal of the Power Terminal
Box and the power wire.
ĺ
Check the normal
operation.
ĺ
End the service.
Replace the fuse.
Yes
Yes
No
After replacing the Inverter PCB of the outdoor
unit, check for normal startup.
ĺ
End the service.
Check the Terminal
Block and Power Terminal Box.
1. Is the screw of the terminal block firmly
Fastened?
2. Are the power wire of the
Power Terminal Box and terminal
firmly assembled?
Is EMI PCB fuse defective?
Yes
Содержание AC071MN4PKH
Страница 12: ...ProductSpecifications 2 9 2 3 4 Filter specifications Item Description CodeNo Remark FILTER AIR DB63 03764A ...
Страница 101: ...PCBDiagramandPartsList 5 4 5 1 3 Outdoor PCB Main PCB AC090 100 120 140MXAD H 1 2 3 4 5 6 8 9 10 11 12 ...
Страница 103: ...PCBDiagramandPartsList 5 6 Outdoor Unit PCB cont PF 4 INVERTER PCB SINGLE PHASE I AC090 100MXADKH 4 1 2 8 3 7 6 5 ...
Страница 105: ...PCBDiagramandPartsList 5 8 Outdoor Unit PCB cont PF 6 1 INVERTER PCB 3 PHASE I AC100MXADNH 1 2 8 4 6 5 3 7 ...
Страница 114: ...6 3 WiringDiagram ThisDocumentcannotbeusedwithoutSamsung sauthorization 3 phase PF 6 PF 6 1 Schematic Diagram ...