Troubleshooting
The table below list the self-diagnostic routines. For some of error codes, you must contact an authorized service
centre.
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER
PCB.
No.
Error Code
Meaning
Remarks
1
E108
Error due to duplicated communication address
Check on repeated indoor unit main address
2
E121
Error on room temperature sensor of indoor unit (Short or
Open)
Indoor unit Room Thermistor Open/Short
3
E122
Error on EVA IN sensor of indoor unit (Short or Open)
Indoor unit EVA_IN Thermistor Open/Short
4
E123
Error on EVA OUT sensor of indoor unit (Short or Open)
Indoor unit EVA_OUT Thermistor Open/Short
5
E153
Error on float switch (2nd detection)
Indoor unit Float Switch Open/Short Drain Pump
operation Check
6
E154
Indoor fan error
Check on indoor unit indoor Fan operation
7
E198
Error on thermal fuse of indoor unit (Open)
Thermal Fuse Open Check of indoor unit
Terminal Block
8
E201
Communication error between the indoor unit and outdoor
unit (Pre-tracking failure or when the actual number of indoor
units are different from the indoor unit quantity setting on
the outdoor unit)
Error due to communication tracking failure after initial power
is supplied (The error occurs regardless of the number of
units.)
Check indoor quantity setting in outdoor
9
E202
Communication error between indoor unit and outdoor unit
(When there is no response from indoor units after tracking is
completed)
Check electrical connection and setting between
indoor unit and outdoor unit
10
E203
Communication error between the outdoor unit and main
micom (For PF #4 to #6 controllers, error will be determined
from the time when the compressor is turned on.)
Check electrical connection and setting between
indoor unit MAIN PBA - INVERTER PBA
11
E221
Error on outdoor temperature sensor (Short or Open)
Check Outdoor sensor Open / Short
12
E231
Error on outdoor COND OUT sensor (Short or Open)
Check Cond-Out sensor Open / Short
13
E251
Error on discharge temperature sensor of compressor 1 (Short
or Open)
Check Discharge sensor Open / Short
14
E320
Error on OLP sensor (Short or Open)
Check OLP sensor Open / Short
15
E403
Compressor down due to freeze protection control
Check Outdoor Cond.
16
E404
System stop due to overload protection control
Check Comp. when it starts
17
E416
System stop due to discharge temperature
-