10
Installation Procedure
English
Ins
tallation Pr
oc
edur
e
Main power terminal block specifications
1-phase terminal block specifications
3-phase terminal block specifications
1(L)
2(N)
L
N
AC power (AC071KXA
✴
EH):
M4 screw
1(L)
2(N)
L
N
AC power
(AC100/125/140KXAPEH) :
M5 screw
1(L)
2(N)
L1(R) L2(S)
L3(T)
N
AC power
(AC100/140KXADGH) :
M5 screw
9.95
11.55
Communication:
M4 screw
F1
F2
Communication:
M4 screw
F1
F2
Main power cable specifications
The power cable is not supplied with air conditioner.
• Select the power supply cable in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power cord and branch wiring are in compliance with local cord.
AC
✴✴✴
K
✴✴
P
✴
H
Type
Model
Outdoor unit
Input current (Amperes)
Power supply
Indoor unit
Outdoor unit
Rated
Voltage range
Outdoor unit
Indoor
unit
Total
MCA
MFA
Hz
Volts
Min
Max
Cooling
Heating
A
AC140KN4PEH/SA AC140KXAPEH/SA
50
220 to 240
198
264
32
32
1.5
33.5
33.5
40
AC125KN4PEH/SP AC125KXAPEH/SP
50
220 to 240
198
264
32
32
1.5
33.5
33.5
40
B
AC100KN4PEH/SA AC100KXAPEH/SA
50
220 to 240
198
264
24
24
1.5
25.5
25.5
30
AC125KN4PEH/SA AC125KXAPEH/SA
50
220 to 240
198
264
24
24
1.5
25.5
25.5
30
C
AC071KN4PEH/SA AC071KXAPEH/SA
50
220 to 240
198
264
22
22
1.5
23.5
23.5
27.5
AC
✴✴✴
K
✴✴
D
✴
H
Type
Model
Outdoor unit
Input current (Amperes)
Power supply
Indoor unit
Outdoor unit
Rated
Voltage range
Outdoor unit
Indoor
unit
Total
MCA
MFA
Hz
Volts
Min
Max
Cooling
Heating
B
AC100KN4DEH/SA AC100KXADGH/SA
50
380 to 415
342
456.5
16.1
16.1
1.5
17.6
17.6
17.6
AC140KN4DEH/SA AC140KXADGH/SA
50
380 to 415
342
456.5
16.1
16.1
1.5
17.6
17.6
17.6
C
AC071KN4DEH/SA AC071KXADEH/SA
50
220 to 240
198
264
20
20
1.5
21.5
21.5
25
NOTE
1
Voltage range
• Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits
2
Maximum allowable voltage variation between phases is 2%.
3
Wire size & type must comply with the applicable
local and national code.
• Wire size: Based on the value of MCA.
• Wire type: 60245 IEC57(IEC) or H05RN-
F(CENELEC) grade or more.
4
MFA is used to select the circuit breaker and the ground
fault circuit interrupter (earth leakage circuit breaker).
5
MCA represents maximum input current.
• MFA represents capacity which may accept MCA
• Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)
360_AC_Outdoor_AU_Eng_EN.indb 10
2016-09-20 오후 8:00:30