Outdoor units
2. Summary Table
Capacity
(Btu/h)
Model Code
Net Size
(WxHxD inch)
Net Weight
(lbs)
Airflow
(CFM)
Sound Pressure Level
(dBA)
Sound Power
Level (dBA)
Cooling
Heating
30,000
CXH24UPB (AC024BXUPCH/AA)
37 x 39-5/16 x 12-1
163
2,684
50
52
70
40,000
CXH36UDB (AC036BXUDCH/AA)
37 x 39-5/16 x 12-1
172
2,684
53
55
73
45,000
CXH36UPB (AC036BXUPCH/AA)
37 x 47-5/8 x 12-1
196
3,531
52
54
73
55,000
CXH48UPB (AC048BXUPCH/AA)
37 x 47-5/8 x 12-1
196
3,531
55
57
75
59,000
CXH60UPB (AC060BXUPCH/AA)
37 x 55-7/8 x 12-1
223
4,414
56
58
75
Model
Outdoor Unit
Input Current (Amperes)
Power Supply
Outdoor Unit
Rated
Voltage range
Outdoor Unit
MCA(A)
MOP(A)
Hz
Volts
Min.
Max
Cooling
Heating
CXH24UPB (AC024BXUPCH/AA)
60
208-230
187
253
11.3
11.5
24.1
30
CXH36UDB (AC036BXUDCH/AA)
60
208-230
187
253
18.0
14.5
24.4
35
CXH36UPB (AC036BXUPCH/AA)
60
208-230
187
253
15.6
15.1
25.6
35
CXH48UPB (AC048BXUPCH/AA)
60
208-230
187
253
24.8
22.2
32.7
40
CXH60UPB (AC060BXUPCH/AA)
60
208-230
187
253
29.8
26.3
33.2
40
Performance Characteristics
Electric Characteristics
•
Sound data is based on cooling operation.
•
MCA : Minimum circuit amperes (A)
•
MOP: Maximum Overcurrent Protective Device (A)
•
Select wire size based on the value of MCA.