32
English
Installation Procedure
Installation Pr
oc
edur
e
• 1) SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.
• 2) SEG8
Even if you set the Use of drain pump option to 0, it is utomatically set to 2 (the drain pump is used with 3
minute delay).
• 3) SEG11
Compensation of the wind-free fan RPM option adjusts 20 rpm per 1 step.
• 4) SEG18
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2
(1000 hours).
Option
SEG19
SEG20
SEG21
SEG22
Function
Page
Individual control with
remote control
5)
Heating setting
compensation
6)
Reserved
Indication
and details
Indication
Details
Indication
Details
Indication
Details
3
0 or 1
Indoor 1
0
Disuse
2
Indoor 2
1
3.6
છ
F (2
છ
C)
3
Indoor 3
2
9
છ
F (5
છ
C)
4
Indoor 4
Option
SEG23
SEG24
Function
Setting the MDS Kit installation option
7)
Reserved
Indication
and details
Indication
Details
0
Disuse (Soft Off+Hard off)
Standard
1
Off after 20 min. (Soft Off+Hard off)
2
Off after 40 min. (Soft Off+Hard off)
3
Off after 80 min. (Soft Off+Hard off)
Premium
4
Off after 20 min. (Soft Off+Hard off)
5
Off after 40 min. (Soft Off+Hard off)
6
Off after 80 min. (Soft Off+Hard off)
Standard
7
Off after 20 min. (Soft Off only)
8
Off after 40 min. (Soft Off only)
9
Off after 80 min. (Soft Off only)
Premium
A
Off after 20 min. (Soft Off only)
B
Off after 40 min. (Soft Off only)
C
Off after 80 min. (Soft Off only)