Setting the installation options in a batch
Installation option No. for an indoor unit address: 02XXXX-1XXXXX-2XXXXX-3XXXXX
1
Make sure that the power is supplied
to the indoor unit. If the indoor unit is
not plugged in, it must include a power
supply.
F1
L(L
1)
N(L2)
F2
V1
V2
F3
F4
Indoor Unit
2
Set the installation options of indoor units, by referring to the following table and by following
the steps in
Common steps for setting the addresses and options
on page
23
.
• The installation options of indoor units are set to 020010-100001-200000-300000 by default.
• The SEG20 option, Individual control with remote control, allows you to control multiple indoor units
individually by using the remote control.
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Reserved
Use of external room temperature sensor /
Minimizing fan operation when thermostat is off
Central control
Compensation of the
fan RPM
Indication
and details
Indication Details Indication Details
Indication
Details
Indication Details Indication Details
Use of
external room
temperature
sensor
Minimizing fan operation when
thermostat is off
1)
0
Disuse
0
Disuse
0
2
0
Disuse
Disuse
1
Use
Disuse
2
Disuse
Use(Heating)
3
Use
Use(Heating)
4
Disuse
Use(Cooling)
5
Use
Use(Cooling)
1
Use
1
High ceiling
mode
6
Disuse
Use
(Cooling/Heating)
7
Use
Use
(Cooling/Heating)
8
Disuse
Use (Cooling Ultra low speed)
9
Use
Use (Cooling Ultra low speed)
A
Disuse
Use (Heating/Cooling Ultra
low speed)
B
Use
Use (Heating/Cooling Ultra
low speed)