9
Appendix
9.1
Function block list
Note!
There are two configuration levels #1 and #2.
Both configuration levels contain the functions F01 to F23 with the specified default settings
and meanings.
The function blocks F01 to F13 have the following listed function.
F = Function block
WE = Default setting
0 = OFF, 1 = ON
F
Function
WE Comment
01 Control mode
1
0 – Fixed set point control
→
Section 6.2
1 – Control with reference variable
→
Section 6.1
02 Selecting the reference
variable
(only effective with F01 - 1)
0
0 – Outdoor sensor
→
Section 6.1
1 – Room sensor
→
Section 6.2
03 Direction of stem action
0
0 – Increasing/increasing
→
Section 6.9
1 – Increasing/decreasing
→
Section 6.9
04 Delayed outdoor
temperature
(only effective with F01 - 1
and F02 - 0)
0
0 – Without delay
1 – With delay
→
Section 6.1.3
05 Potentiometer input
0
0 – Inactive, binary input active
→
Section 6.3.1
1 – Active
→
06 Resistance range of
potentiometer
(only effective with F05 - 1)
0
0 – Type 5257-7 Room Panel (1000 to 1100 ohm)
→
1 – Type 5257-2 w. remote adjuster (1000 to 2000 ohm)
→
Section 6.1.1
07 Function of potentiometer
(only effective with F02 - 0
and F05 - 1)
0
0 – Heating characteristic level shift
→
Section 6.1.1
1 – Gradient shift
→
Section 6.1.1
08 Function of binary input
(only effective with F05 - 0)
0
0 – BI short-circuited: OFF w. frost protection
→
Section 6.3.1
1 – BI short-circuited: Reduced operation
→
Section 6.3.1
52
EB 5757-7 EN
Appendix