Function
WE
Configuration
Underfloor heating
OFF
25.0 °C
5.0 °C/day
45.0 °C
4 days
0.0 °C/day
0
HC1–CO1–05 = ON
Start temperature for drying of jointless floors /
20.0 to 60.0 °C
Temperature increase for drying of jointless floors /
1.0 to 10.0 °C/day
Max. temperature for drying of jointless floors /
2.0 to 60.0 °C
Max. temperature sustaining time for drying of jointless
floors / 1 to 10 days
Temperature reduction for drying of jointless floors /
0.0 to 10.0 °C/day
Start drying of jointless floors / 0 to 5 (meaning of 0 to 3
on page 59, 4 = drying process successfully completed,
5 = too large system deviation during drying process
occurred
6.4
Deactivation based on the outdoor temperature
6.4.1 HC deactivation value (day)
If the outdoor temperature exceeds 'HC1 deactivation value (day)', the heating circuit is imme-
diately deactivated. The valve is closed and the pump is switched off after t = 2 x valve transit
time. When the outdoor temperature falls below this value (less 0.5 °C hysteresis), heating oper-
ation is restarted immediately.
The default setting causes the system to be deactivated during the warm season when the out-
door temperature reaches 22.0 °C.
Parameter
WE
Parameter settings
HC1 deactivation value (day)
22.0 °C
Refer to section 3.1
6.4.2 HC deactivation value (night)
If the outdoor temperature exceeds 'HC1 deactivation value (night)' outside the times-of-use, the
heating circuit is immediately deactivated. The valve is closed and the pump is switched off after
t = 2 x valve transit time. When the outdoor temperature falls below this value (less 0.5 °C hyster-
esis), heating operation is restarted immediately.
The default setting causes the system to be deactivated when the outdoor temperature reaches
15.0 °C at night to save energy. However, it is important tor remember that the system requires
some time in the morning to heat up the building.
60
EB 5610 EN
Functions of the heating circuit
Содержание trovis 5600
Страница 22: ...22 EB 5610 EN Setup settings B C D A A...
Страница 124: ...124 EB 5610 EN...
Страница 125: ...EB 5610 EN 125...
Страница 126: ...126 EB 5610 EN Key number 1732...