DHW–
CO4–
Function
Anl
WE
Comment
Function block parameters
/ Range of values
06
Parallel pump
operation
Only Anl.
2.1.0
2.2.0
OFF
OFF: Function inactive
ON: Parallel pump operation
Function block can only be selected when
• DHW–CO4–07 = OFF
10 min
40.0 °C
Function block parameters:
Delay of cancelation due to system deviation /
0 to 10 min
Min. flow set point in heating circuit for parallel pump
operation / 20.0 to 90.0 °C
07
Intermediate
heating
Only Anl.
2.0.0
2.1.0
2.2.0
ON
OFF: Storage tank charging unrestricted; heating opera-
tion with UP1 has priority over DHW heating
ON: DHW limited to 20 minutes, then 10 minutes
heating operation with P1 (UP)
Function block can only be selected when
• DHW–CO4–06 = OFF
08
Priority by re-
verse control
Only Anl.
1.1.0
1.1.1
1.2.0
11.0.0
11.2.0
11.9.0
11.9.1
OFF
OFF: Function inactive
ON: Priority by reverse control active, only when
• DHW–CO4–09 = OFF
2 min
1.0
Function block parameters:
Delay of reverse control active / 0 to 10 min
Correction factor / 0.1 to 1.0
09
Priority by
set-back
operation
Only Anl.
1.1.0
1.1.1
1.2.0
11.0.0
11.2.0
11.9.0
11.9.1
OFF
OFF: Function inactive
ON: Priority by set-back operation active, only when
• DHW–CO4–08 = OFF
2 min
Function block parameter:
Delay of set-back operation active / 0 to 10 min
10
Circulation re-
turn flow in
heat exchanger
Only Anl.
1.6.0
1.6.1
1.6.2
OFF
OFF: Function inactive
ON: Active control of DHW heating when circulation
pump is active
11
Circulation
mode during
storage tank
charging
Only Anl.
1.9.0
1.9.1
11.0.0
11.9.0
11.9.1
OFF
OFF: Function inactive
ON: Circulation pump runs during storage tank
charging according to time schedule
EB 5610 EN
105
Appendix