Parameter
WE
Adjustment range
Regelkreis (control circuit)
= stetig (continuous)
3-Punkt
Continuous, three-step
2
[Übersicht > Parameter > Wärmetauscher 1…3]
Parameters
WE
Adjustment range
Kp
1.0
0.1 bis 99.9
Tn
30 s
0 bis 999 s
Tv
0 s
0 bis 999 s
Ty
45 s
15 bis 600 s
Heating circuits HK1 to HK3
The continuous signal is issued by the following binary outputs:
4
AA6 at ModBus I/O 1402-0328 (1) for heating circuit HK1
4
AA6 at ModBus I/O 1402-0328 (2) for heating circuit HK2
4
AA6 at ModBus I/O 1402-0328 (3) for heating circuit HK3
Note:
Alternative assignment is shown in section 8.1.
2
[Übersicht > Service > Heizkreis 1…3]
This menu can only be selected after the application key number has been entered!
Parameter
WE
Adjustment range
Regelkreis (control circuit)
= stetig (continuous)
3-Punkt
Continuous, three-step
2
[Übersicht > Parameter > Heizkreis 1…3]
Parameters
WE
Adjustment range
Kp
6.0
0.1 to 99.9
Tn
120 s
0 to 999 s
Tv
0 s
0 to 999 s
Ty
120 s
5 to 600 s
EB 5571-2 EN
41
General functions