EB 8389 EN
69
Tests
waiting 30 seconds using the new oper-
ating point.
−
If this test is also canceled by a
change
in set point (∆w)
, it is reactivated after
waiting 60 seconds using the new oper-
ating point.
−
The test is started again ten times at the
maximum. The time between tests is in-
creased by 30 seconds each time (30 s x
Number of tests repeated). After the
tenth time that the test is canceled, the
time entered in 'Min. time distance from
test' is kept again.
If the analysis of the hysteresis pinpoints
'Friction', the positioner generates a corre-
sponding status message.
Diagnosis > Status messages > Extended
−
Friction
5.2.2 Resetting single status
messages
The diagnostic parameters and measured
data analysis from the 'Drive signal diagram
hysteresis' test are reset by selecting and ex-
ecuting the command "Reset 'Drive signal di-
agram hysteresis measured data'".
Operation > Reset
−
Reset 'Drive signal diagram – hysteresis –
measured data'