![Samson STL 5345 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/samson/stl-5345/stl-5345_mounting-and-operating-instructions_806321006.webp)
6
EB 5206 EN
Design and principle of operation
Type
Set point range
Switching
differential
approx. Switching point accuracy
Max.
medium
temp.
Safety temperature monitor (STM)
5343-1
0 to +60 °C
8 K
Range
Range
0 to +30 °C:
+30 to +60 °C:
+0 K
+0 K
–12 K
–5 K
+85 °C
5343-2
+40 to +100 °C
8 K
Range
Range
+40 to +70 °C:
+70 to +100 °C:
+0 K
+0 K
–5 K
–12 K
+125 °C
5343-3
+70 to +130 °C
8 K
Range
Range
+70 to +100 °C:
+100 to +130 °C:
+0 K
+0 K
–5 K
–12 K
+155 °C
5343-4
+35 to +95 °C
8 K
Range
Range
+35 to +65 °C:
+65 to +95 °C:
+0 K
+0 K
–5 K
–12 K
+120 °C
Temperature regulator (TR)
5344-1
0 to +120 °C
3 K
Range
Range
0 to +60 °C:
+60 to +120 °C:
+6 K
+3 K
–6 K
–3 K
+145 °C
5344-2
+20 to +150 °C
4 K
Range
Range
+20 to +85 °C:
+85 to +150 °C:
+6 K
+3 K
–6 K
–3 K
+175 °C
Safety temperature limiter (STL)
5345-1
+70 to +130 °C
10 K
Range
Range
+70 to +100 °C:
+100 to +130 °C:
+0 K
+0 K
–5 K
–12 K
+155 °C
5345-2
+30 to +90 °C
10 K
Range
Range
+30 to +60 °C:
+60 to +90 °C:
+0 K
+0 K
–5 K
–12 K
+115 °C
Double thermostat TR/STL
5347-1
TR: 0 to +120 °C
3 K
Range
Range
0 to +60 °C:
+60 to +120 °C:
+6 K
+3 K
–6 K
–3 K
+145 °C
STL: +70 to +130 °C
8 K
Range
Range
+70 to +100 °C:
+100 to +130 °C:
+0 K
+0 K
–5 K
–12 K
Double thermostat TR/STM
5348-1
TR: 0 to +120 °C
3 K
Range
Range
0 to + 60 °C:
+60 to +120 °C:
+6 K
+3 K
–6 K
–3 K
+145 °C
STM: +70 to +130 °C
8 K
Range
Range
+70 to +100 °C:
+100 to +130 °C:
+0 K
+0 K
–5 K
–12 K
Double thermostat STM/STL
5349-1
STM: +70 to +130 °C
8 K
Range
Range
+70 to +100 °C:
+100 to +130 °C:
+0 K
+0 K
–5 K
–12 K
+145 °C
STL: +70 to +130 °C
8 K
Range
Range
+70 to +100 °C:
+100 to +130 °C:
+0 K
+0 K
–5 K
–12 K
Содержание STL 5345
Страница 18: ...18 EB 5206 EN...
Страница 19: ...EB 5206 EN 19...