![Samson STL 5345 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/samson/stl-5345/stl-5345_mounting-and-operating-instructions_806321005.webp)
2.2
Technical data
EB 5206 EN
5
Design and principle of operation
Single thermostats:
Type 5343 (STM), Type 5344 (TR), Type 5345 (STL)
Double thermostats:
Type 5347 (TR/STL), Type 5348 (TR/STM), Type 5349 (STM/STL)
Permissible ambient temperature
Transportation and storage
–30 to +50 °C
Service
Max. +80 °C
Max. pipe temperature when
mounted as a contact thermostat
Max. +120 °C
Degree of protection
IP 54 according to EN 60529
Cable entry
M20 x 1.5 cable gland,
suitable for 6 to 12 mm cable diameter
Minimum switching capacity
AC/DC = 24 V, 100 mA
Maximum switching capacity
Temperature regulator (TR),
Safety temperature monitor (STM)
With 230 V AC
+10 %
NC contact:
NO contact:
16 A (2.5); cos
ϕ
= 1 (0.6)
6.3 A (2.5); cos
ϕ
= 1 (0.6)
With 230 V DC
+10 %
NC contact:
NO contact:
0.25 A
0.25 A
Safety temperature limiter (STL)
With 230 V AC
+10 %
NC contact:
Signal contact:
16 A (2.5); cos
ϕ
= 1 (0.6)
2 A (2.5); cos
ϕ
= 1 (0.4)
With 230 V DC
+10 %
NC contact:
Signal contact:
0.25 A
0.25 A
Influence of mean ambient
temperature based on the set point
A shift of the switching point arises when the ambient temperature
at the knob and at the capillary deviates from the calibration am-
bient temperature of +22 °C:
Higher ambient temperature
→
Lower switching point
Lower ambient temperature
→
Higher switching point
This influence is minimized by temperature compensation.
Connection
Spring-clamp terminals, 0.75 to 2.5 mm² wire cross-section
Materials
Bottom section of the housing
PA (reinforced)
Housing cover
ABS with window (PMMA)
Bulb and capillary
Cu (copper)
Weight
Single thermostat approx. 0.225 kg
Double thermostat approx. 0.45 kg