Malfunctions
8
Malfunctions
8.1
Troubleshooting
To identify the exact cause for the malfunction and to rectify it, the associated valve must also
be taken into account. Full troubleshooting instructions are listed in the corresponding mount-
ing and operating instructions of the regulator (see documents listed under 'Referenced docu-
mentation' in the 'Safety instructions and measures' section).
Malfunction
Possible reasons
Recommended action
Temperature at the
sensor exceeds or
falls below the set
point.
Sensor installed in the wrong location.
Î
Change the mounting position.
Sensor installed incorrectly.
Î
Immerse the temperature sensor with its entire
immersion depth in the process medium.
Î
Avoid an installation site where idle times or
heat buildup can occur.
Control thermostat defective
Î
Replace the control thermostat.
Temperature at the
sensor fluctuates.
Sensor installed in the wrong location.
Î
Change the mounting position.
Sensor installed incorrectly.
Î
Immerse the temperature sensor with its entire
immersion depth in the process medium.
Î
Avoid an installation site where idle times or
heat buildup can occur.
Slow control re-
sponse
Time constant is too large for the control
loop.
Î
Fill the thermowell with thermal paste or re-
move the thermowell.
Î
Use a sensor with smaller time constant (e.g.
vapor pressure thermostat).
Sensor installed incorrectly.
Î
Immerse the temperature sensor with its entire
immersion depth in the process medium.
Î
Avoid an installation site where idle times or
heat buildup can occur.
Leak between con-
trol thermostat and
valve
Valve seal defective
Î
Contact SAMSON's After-sales Service.
Contact SAMSON's After-sales Service for malfunctions not listed in the table.