EB 5827-2 EN
16-3
Annex A (configuration instructions)
The error message is reset and the actuator returns to closed-loop operation if the input sig-
nal moves within 0.2 V or 0.4 mA of the lower range value.
Settings\Actuator\Functions
Functions
WE
Adjustment range
Detect input signal failure
No
Yes/No
Positioning value upon input signal failure
Internal
Internal, last position
Internal positioning value
0.0 %
0.0 to 100.0 %
16.3.2
End position guiding
The actuator stem moves to the end position earlier if the end position guiding function is
active.
−
'Value below limit (end position guiding)'
The actuator stem moves to the 0 % position when the input signal falls below 'Value
below limit (end position guiding)'.
−
'Value above limit (end position guiding)'
The actuator stem moves to the 100 % position when the input signal falls below 'Value
above limit (end position guiding)'.
When 'Value below limit (end position guiding)' = 0 % and 'Value above limit (end position
guiding)' = 100 %, the end position guiding function is deactivated.
Settings\Actuator\Functions
Functions
WE
Adjustment range
Value below limit (end position guiding)
1.0 %
0.0 to 49.9 %
Value above limit (end position guiding)
97.0 %
50.0 to 100.0 %
Note
Содержание 5827
Страница 6: ...6 EB 5827 2 EN...
Страница 22: ...3 8 EB 5827 2 EN...
Страница 42: ...7 4 EB 5827 2 EN...
Страница 56: ...9 4 EB 5827 2 EN...
Страница 58: ...10 2 EB 5827 2 EN...
Страница 60: ...11 2 EB 5827 2 EN...
Страница 64: ...12 4 EB 5827 2 EN...
Страница 66: ...13 2 EB 5827 2 EN...
Страница 68: ...14 2 EB 5827 2 EN...
Страница 70: ...15 2 EB 5827 2 EN Certificates EU declaration of conformity...
Страница 74: ...15 6 EB 5827 2 EN Certificates...
Страница 84: ...16 10 EB 5827 2 EN...
Страница 88: ...17 4 EB 5827 2 EN...
Страница 89: ......
Страница 90: ......
Страница 91: ......